Section: Global DC
The purpose of this section is to describe the global DC alarms.
*In the event that the alarm becomes active, it will remain active until the release threshold value is reached
Item | The Affected Digital Alarm/Dashboards | Default Values |
---|---|---|
Voltage Threshold LVD | Â Site_Global.DC_Alarm_LVD Â | 43.5Â V |
Voltage Threshold LVD Release | Â 49V | |
Voltage Threshold BLV | Â Site_Global.DC_Alarm_BLV Â | Â 48V |
Voltage Threshold BLV Release | Â 50V | |
Voltage Threshold PLD | Â Site_Global.DC_Alarm_PLD Â | Â 45.5V |
Voltage Threshold PLD Release | 51V | |
Voltage Threshold Generator Fail To Start | Site_Global.Generator_X_Fail_To_Start *Hard coded release - 49.3V | 48.3V |
Â