Active/Recorded Digital Inputs

Field Name

Field Meaning and Logic

Field Name

Field Meaning and Logic


Generator_X.Engine_Hours_Tampering

The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours.
[2 < (ABS(engine hours difference - time difference].

Generator_X.Alarm Internal Frequency High

The digital field will be active when the following conditions are met:
Site Global Generator Running is active AND (Alarm_Internal is true OR (Generator_X.Frequency is greater than the High Frequency Threshold AND the High Frequency Threshold is greater than 0)).

Generator_X.Alarm Galooli Frequency Low

The digital field will be active when the following conditions are met:
(Site Global Generator Running AND (Alarm_Internal is true OR 0 < Generator_X.Frequency < Low Frequency Threshold

Generator_X.Alarm Galooli Low Oil Pressure

The digital field will be active when the following conditions are met:
(Site Global Generator Running AND (Alarm_Internal is true OR 0 < Oil Pressure < Low Oil Pressure Threshold

Generator_X.Alarm Galooli High Coolant Temperature

The digital field will be active when the following conditions are met:
Site Global Generator Running AND (Alarm_Internal is true OR (Coolant Temp > High Coolant Temp Threshold AND High Coolant Temp Threshold> 0))

Generator_X.Alarm Galooli Short Circuit Current

The digital field will be active when the following conditions are met:
Alarm Internal Short Circuit OR (Max(Generator Current L_1..3) > Short Circuit Current Threshold AND Short Circuit Current Threshold > 0))

Generator_X.Alarm Galooli Over Circuit Current

The digital field will be active when the following conditions are met:
Alarm Internal Over Current OR (Max(Generator Current L_1..3) > Over Circuit Current Threshold AND Over Circuit Current Threshold > 0))

Rectifier_X.Alarm_Surppressed

It is an alarm from the rectifier that indicates that other alarms have been configured not to be active, leading to alerts not being received by the user.

Site_Global.Alarm Galooli Generator X High Load

 

Site_Global.Alarm Galooli Generator X Very High Load

 

Site_Global.Alarm Galooli High Battery Current

The alarm will be activated if the unit is set to "Global DC.High Battery Current Threshold" AND "Site_Global.Battery_Current [A] > Global DC.High Battery Current Threshold"

Site_Global.Alarm Galooli High System Voltage

The alarm will be activated if the unit is set to “Global DC.High System Voltage Threshold” AND “Site_Global.U_System [V] > Global DC.High System Voltage Threshold”


Rectifier_X.Alarm Internal Solar SPD Fail

This alarm is displayed when there is an (internal) fault in the 'lightning protection' mechanism (which keeps electrical devices from being damaged by high current surges like lightning). In this case, it is the entry of diesel current into the rectifier. For Eltek smartpack 2 touch rectifiers only.