Site Status Card
The site status includes information regarding the main parameters of each energy asset on site - the Grid, Generator, Solar, Wind and Battery. Furthermore, it will display the contribution of each energy asset to the site's load and the load's power. The display of each asset will be independent of the others, and will only appear if:
Grid – If the sites layout includes the text “On Grid”
Generator – According to Generator 1/2 Panel, or Configuration->Generator1/2 Running, or if Fuel_1/2 is configured
Solar - If the sites layout includes the text “Solar”
Wind - If the sites layout includes the text “Wind”
Battery - If the site layout includes the text "Storage"
Site Status data is based on global fields.
Main View
There will be power data associated with each element (Grid/Generator/Battery/Solar/Wind). kW refers to the amount of power flowing from the source to the consumer.
A dark blue color will be applied to elements that are under load, and a light blue color will be applied to other elements.
Load percentages will only be displayed for elements that are on load.
When Site_Global.Grid_on_Load is true -> flow direction is from the grid to the site icon
Grid Export -
When Site_Global.Grid_Power < 0 -> flow direction is from the site icon to the grid.
If Site_Global.Grid_Power < 0 is true, the text "Export" above the icon will appear (instead of the percentages)
In the event that Site_Global.Battery_Charging is true, instead of percentages, the text "Charging" will be displayed, and the battery's icon color will remain dark blue.
The generator load is calculated as follows: Site_Global.1_Load [%] + Site_Global.2_Load [%]
When elements are on load (X_On_Load == True), their line will move toward the site's icon (Generator1_On_Load or Generator2_On_Load for generator icons). When the battery is charging (Site_Global.Battery_Charging), the line will move from the icon to the battery.
The text "Unknown On Load" will be displayed next to the site's main icon if the unknown source is loaded ("Site_Global.Unknown_On_Load = True)
Consumers Load - appears below the site icon (Site_Global.Consumers_Load_Power). Adds up all the power consumed on site. Accordingly, the result value is the product of the tenants' power and the rectifiers' power, as well as the power of all the air conditioners on the premises.
Alarms Indicators - Amount and color of alarms over the relevant energy asset. In the event that there is more than one alarm, the color of the most critical alarm will be displayed:
Grid - Grid Partly Available, Grid Fail, Grid High Voltage
Generator - Fuel_1,2 Disconnected, Fuel_1,2 Low, Fuel 1,2 Very Low, Alarm FuelTank Hatch_1,2, _1,2 Fail To Start, _1,2 Fail To Stop, Running Batt Discharge
Wind - No alarms on-site global
Battery - DC Alarm BLV, DC Alarm PLD, DC Alarm LVD
Solar - No alarms on-site global
Expanded View
In the expanded view of the Site Status Card, you will be able to see additional details that are not presented in the main view.
The site location is part of the expanded view of the Site Status Card. The map presenting the real-time location and movement of your units on the map.
The map view can be switched between satellite view and map view.
It is a Google map that includes a variety of features.