NOC Alarms List

NOC Alarms List

NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. You can get a good idea of the extreme conditions on site based on the alarms. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.

System Thresholds - NOC alarms are affected by Galooli "System Thresholds", which can be changed by the user through the Galooli Solution. The NOC alarm types listed below include system thresholds data. My Units

Power Alarms

Alarm Name

Description

System Parameter Name

System Thresholds

AC Meter Grid Low PF

In order to ensure that there are no false alarms regarding the AC meter grid low power factor at least in one phase, the system checks that the PF is greater than 0 and the current of the phase is higher than 1.

  • 0 < ABS(AC_Meter_Grid.PF_LX) < 0.8 (The absolute value of the power factor is greater than 0 and less than 0.8)

AND

  • ABS(AC_Meter_Grid.I_LX) > 1[A] (The absolute value of the current is greater than 1)

 

Battery High Current

The alarm is true if the digital 'Site Global Alarm High Battery Current' is true.

Site_Global.Alarm Galooli High Battery Current

  • High Battery Current Threshold

 

BLV Alarm 

This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold - Global DC

 

Site_Global.Alarm Galooli DC BLV

  • Voltage Threshold BLV

  • Voltage Threshold BLV Release

 

 

 

Consumers' Load Drop

If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active.

As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report).

 If (Unit KPI Field)‘Consumers Load Drop Current Threshold'> 0, check if 'Site Global Consumers Load Power' < (Site Global U System’ * threshold

Site_Global.Alarm Galooli Consumers Load Drop

 

  • Consumers Load Drop Current

Consumers Load High 

The alarm is true if 'Site Global Consumers Load Power' > threshold, and threshold > 0.

Threshold - unit KPI → Consumers → ‘High Consumers Power Threshold

Site_Global.Consumers_Load_Power [W]

  • High Consumers Power Threshold

Generator is Running at Solar Site

The site is running on generator more that X hours strait and this is a solar hybrid site

Starting from Mar 17, 2026, the alarm logic was updated so that the alert is no longer triggered automatically after 10 hours.
Instead, the time until the alarm is triggered is now determined by the value defined in the Activation Delay field in the alarm settings under My NOC.

For alarms that were configured before Mar 17, 2026 and the Activation Delay value was set to 0, the system automatically updates it to 600 minutes (10 hours)

Time In Status

Site Layout

 

 

Generator Running

 

The alarm is triggered when at least one generator on the site is running.

 

Site Global.Generator_X_Running

The alarm timing is controlled by the configured Activation Delay.
Users can define the required delay according to their operational needs.

Generator running and battery discharging

The Generator running but battery is discharging

Site_Global.Alarm Galooli Generator Running Battery Discharge

 

Generator Running and Battery not Charging

If site is hybrid AND ‘Site Global.Generator_1-2_Running’ AND ‘Site Global.Battery Charging’ is false

Site Global.Generator_X_Running
and
Site Global.Battery Charging

 

Generator Running While Grid Fully Available

 Generator running = True AND Grid Available = True AND Grid Partialy Avilable = False

Site_Global.Alarm Galooli Generator Running Grid Fully Available

 

Generator is Running at Solar or Hybrid Site

Generator is running and the layout is Solar or Hybrid

Site Global.Generator_X_Running

Layout

 

Grid High Current

The alarm is true if for at least one phase ABS(Site Global Grid_I1-3) > threshold, and threshold > 0.

Threshold - unit KPI → Grid → 'High Current Threshold

Site Global Grid_I1-3 > threshold, and threshold > 0.

 

Grid High Voltage

Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid exceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active.
Grid*

Site Global Alarm Galooli Gird_High_Voltage

  • High Voltage Threshold

Grid Partly Available

Grid only partly available indication - https://galooli.atlassian.net/wiki/x/CwDYt

Site_Global.Alarm Galooli Grid Partly Available

 

High Battery Temperature

Rectifier's internal High Battery Temp  alarm

Rectifier_X.Alarm Internal Battery Temperature

Temperature sensor is configured and battery temperature exceeds 37°C.

High System DC Voltage

The alarm is true if the digital 'Site Global Alarm High System Voltage’ is true.

Site_Global.Alarm Galooli High System Voltage

  • High System Voltage Threshold

Low Solar Power

Triggered when the site is configured with solar power and the current solar power production is significantly lower than expected during daytime hours. It is triggered when solar power drops below 25% of the average solar power trend, based on the unit time.

No Solar Power NOC alarm is False AND Site layout contains Solar AND unit time is 7:00-17:00 and Site_Global.Solar_Power [W] < 25% of Average Solar power (trends-15 min solar avg power)

 

 

LVD  Alarm 

This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. Global DC

At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage.

 

Site_Global.Alarm Galooli DC LVD

  • Voltage Threshold LVD

  • Voltage Threshold LVD