NOC Alarms List
NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. You can get a good idea of the extreme conditions on site based on the alarms. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.
System Thresholds - NOC alarms are affected by Galooli "System Thresholds", which can be changed by the user through the Galooli Solution. The NOC alarm types listed below include system thresholds data. My Units
Power Alarms
Alarm Name | Description | System Parameter Name | System Thresholds |
AC Meter Grid Low PF | In order to ensure that there are no false alarms regarding the AC meter grid low power factor at least in one phase, the system checks that the PF is greater than 0 and the current of the phase is higher than 1. |
AND
|
|
Battery High Current | The alarm is true if the digital 'Site Global Alarm High Battery Current' is true. | Site_Global.Alarm Galooli High Battery Current |
|
BLV Alarm | This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold - Global DC |
Site_Global.Alarm Galooli DC BLV |
|
Consumers' Load Drop | If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active. As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report). If (Unit KPI Field)‘Consumers Load Drop Current Threshold'> 0, check if 'Site Global Consumers Load Power' < (Site Global U System’ * threshold | Site_Global.Alarm Galooli Consumers Load Drop |
|
Consumers Load High | The alarm is true if 'Site Global Consumers Load Power' > threshold, and threshold > 0. Threshold - unit KPI → Consumers → ‘High Consumers Power Threshold | Site_Global.Consumers_Load_Power [W] |
|
Generator is Running at Solar Site | The site is running on generator more that X hours strait and this is a solar hybrid site Starting from Mar 17, 2026, the alarm logic was updated so that the alert is no longer triggered automatically after 10 hours. For alarms that were configured before Mar 17, 2026 and the Activation Delay value was set to 0, the system automatically updates it to 600 minutes (10 hours) | Time In Status Site Layout |
|
Generator Running |
The alarm is triggered when at least one generator on the site is running. |
Site Global.Generator_X_Running | The alarm timing is controlled by the configured Activation Delay. |
Generator running and battery discharging | The Generator running but battery is discharging | Site_Global.Alarm Galooli Generator Running Battery Discharge |
|
Generator Running and Battery not Charging | If site is hybrid AND ‘Site Global.Generator_1-2_Running’ AND ‘Site Global.Battery Charging’ is false | Site Global.Generator_X_Running |
|
Generator Running While Grid Fully Available | Generator running = True AND Grid Available = True AND Grid Partialy Avilable = False | Site_Global.Alarm Galooli Generator Running Grid Fully Available |
|
Generator is Running at Solar or Hybrid Site | Generator is running and the layout is Solar or Hybrid | Site Global.Generator_X_Running Layout |
|
Grid High Current | The alarm is true if for at least one phase ABS(Site Global Grid_I1-3) > threshold, and threshold > 0. Threshold - unit KPI → Grid → 'High Current Threshold | Site Global Grid_I1-3 > threshold, and threshold > 0. |
|
Grid High Voltage | Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid exceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active. | Site Global Alarm Galooli Gird_High_Voltage |
|
Grid Partly Available | Grid only partly available indication - https://galooli.atlassian.net/wiki/x/CwDYt | Site_Global.Alarm Galooli Grid Partly Available |
|
High Battery Temperature | Rectifier's internal High Battery Temp alarm | Rectifier_X.Alarm Internal Battery Temperature | Temperature sensor is configured and battery temperature exceeds 37°C. |
High System DC Voltage | The alarm is true if the digital 'Site Global Alarm High System Voltage’ is true. | Site_Global.Alarm Galooli High System Voltage |
|
Low Solar Power | Triggered when the site is configured with solar power and the current solar power production is significantly lower than expected during daytime hours. It is triggered when solar power drops below 25% of the average solar power trend, based on the unit time. | No Solar Power NOC alarm is False AND Site layout contains Solar AND unit time is 7:00-17:00 and Site_Global.Solar_Power [W] < 25% of Average Solar power (trends-15 min solar avg power) |
|
LVD Alarm | This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. Global DC At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage. |
Site_Global.Alarm Galooli DC LVD |
|