NOC Alarms List

NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. Based on the alarms, you can get a good idea of what extreme conditions are on site. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.

Environment Alarms

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

 

 

 

 

 

Environment

A/C Fault

At least 1 of the Shelter A/C alarm is active

Active Digital Input

Shelter_X.ACY_Alarm

X =1 → 5
Y =1 → 3

2

AWL Fault

Aviation/Aircraft Warning Light is OFF

Active Digital Input

Site_Global.Aviation_Light_Fail

 

3

Fence Alarm

Fence intrusion detection alarm is active

Active Digital Input

Site_Global.Fence_alarm_True

 

4

Gate Alarm

The alarm is active if at least one of the alarms (Entrance/Fence) is true.

Active Digital Input

Site_Global.Entrance_Alarm

 

5

High temp General

At least 1 shelter temperature is above the set high-temperature threshold

Active Digital Input

Shelter_X.Alarm_Temperature

X = 1 → 5

6

High temp Shelter X

Temperature is above the set high-temperature threshold

Active Digital Input

Shelter_X.Alarm_Temperature

X = 1 → 5

7

Intrusion Alarm 

At least 1 of the Shelter Door is Open

Active Digital Input

 Shelter_X.Door_Open

 X = 1 → 5

8

Smoke Alarm

At least 1 of the Shelter Smoke alarms is active in 1 or more of the 5 shelters

Active Digital Input

Shelter_X.Smoke_Alarm

 X = 1 → 5

9

Very High temp General

At least one shelter temperature is above the set Very-high-temperature threshold

 Active Digital Input

 ShelterX.Alarm_temperature_VeryHigh

 X = 1 → 5

10

Very High temp Shelter X

Temperature is above the set Very high-temperature threshold.

Active Digital Input

 ShelterX.Alarm_temperature_VeryHigh

 X = 1 → 5

Fuel Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

 

1

 

 

Fuel

 

Fuel  Drop

Fuel drop of 10 liters and above. The alarm is deactivated after 1 hour.

The data is recorded and displayed in the Galooli solution until the next drop.

 

Additional Info

 

Generator.Fuel Alerts.Last Drop

 

2

Level Low

1 of the fuel level is low

Active Digital Inputs

Site_Global.Alarm_Fuel_X_Low

 X = 1 → 2

3

Level Very Low

1 of the fuel level is very low

Active Digital Inputs

Site_Global.Alarm_Fuel_X_VeryLow

 X = 1 → 2

Generator Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

 

 

 

 

 

 

 

 

Generator

Battery low

At least one of the generators battery voltage is low

Active Digital Input

Generator_X.Battery_low

 X = 1 → 2

 

2

Generator Controller Fault

No communication between the Gen controller and Galooli RTU, controller data is not available.

Active Digital Input

Generator_X.Disconnected

 X = 1 → 2




3

 

Generator Fail to start

  • For hybrid sites: the alarm will be active when DC voltage (Site Global.U_System) ≤ Generator fail to start threshold and Gen is “off” and another power source not available.

  • For non-hybrid sites: the alarm will be active if “Site_Global.AC_Fail” is “True”, or “Generator_1.Fail_To_Start” is “True” (reading from the generator panel)

 

Active Digital Input

Site_Global.DGX_Fail_To_Start

 X = 1 → 2 

4

Generator Fail to stop

Grid available and Generator is running or Generator_1.Fail_To_Stop is true (reading from the generator panel)

Active Digital Input

Site_Global.Generator_X_Fail_To_Stop

 X = 1 → 2 

5

Generator Fault

At least 1 Generator alarm is on

 Active Digital Input

(Generator_X.Alarm_Active) && !(Generator_X.Fail_to_start)

  X =1 → 2 

6

Generator Running > 10 Hours at Solar Hybrid Site

The site is running on generator more that 10 hours strait and this is a solar hybrid site

Active Status

Unit

Time In Status>10 Hours

Site Layout = Solar

 

7

Generator Running When Grid Available

Gen is running and Grid is available simultaneously for at least 25 minutes

Active Status 

Active Digital Input

Time In Status>25 Minutes

Site_Global.Grid_Avialable

 

8

Emergency Stop

Generator Emergency Stop occurred

 Active Digital Input

Generator_X.Emergency_stop

 X =1 → 2 



9



Engine Hours Tampering

The alarm become active when the difference in engine hours exceeds the difference in records by more than two hours.

It is essential that the NOC alarm is configured with an “Activation Delay time: 0” and a long “Release Delay time” in order to detect the alarm effectively (the above flag will only be True for one transmission of the unit and will be canceled by the time of the next transmission).

Active Digital Input

Generator_X.Engine_Hours_Tampering

 X =1 → 2 

10

High Coolant

Generator High Coolant indication

 Active Digital Input

Generator_X.High_coolant

 X =1 → 2 

11

High Voltage

Generator High Voltage indication

 Active Digital Input

Generator_X.High_voltage

 X =1 → 2 

12

Low Oil Pressure

Generator Low Oil Pressure Indication

 Active Digital Input

Generator_X.Low_oil_Pressure

X =1 → 2

13

Not in Auto

Generator Not in Auto mode

 Active Digital Input

Generator_X.Not_in_AutoMode

X =1 → 2

14

Low Voltage

Generator Low Voltage indication

 Active Digital Input

Generator_X.Low_voltage

 X =1 → 2 

15

Over Frequency

Generator Over Frequency indication

 Active Digital Input

Generator_X.Over_frequency

X =1 → 2

GPS Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

GPS

Tracking

Sparta unit, working mode In Tracking alarm

Active Digital Input

Battery_State.Tracking

 

Hardware Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

 

 

 

 

Hardware

ATS Meter Disconnected

No communication between ATS Meter and the Galooli RTU

Active Digital Input

AC_Meter_ATS.Disconnected

 

2

Extension Disconnected

One of the extensions is disconnected

Active Digital Input

Site_Global.EX20ETH_X_Disconnected || Site_Global.EX20_X_Disconnected

 X =1 → 5 

3

Fuel Sensor Disconnected

No communication between the Fuel sensor and the Galooli RTU

Active Digital Input

Site_Global.Fuel_X_Disconnected

 X =1 → 2  

4

Temperature Sensor Fault

The temperature sensor in at least 1 of the shelter is out of range, mostly not real

Active Analog Input

(Shelter_X.Room_Temperature > 55) || (Shelter_X.Room_Temperature < 0)

 X =1 → 5 

5

Tenant 1 - 20
Meter Disconnected

At least 1 of the 20 Tenant meters is currently Disconnected

Active Digital Input

 Colo_Meter_X.Disconnected

X=1 → 10

6

Unit Disconnected

No communication between Galooli RTU and the server

Active Status

Status = Disconnected

 

Power Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

BLV Alarm 

This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold

Active Digital Input

 Site_Global.DC_Alarm_BLV

 

2

DG running and battery discharging

The DG running but battery is discharging

Active Digital Input

Site_Global.Alarm_DG_Running_Bat_Discharge

 

3

Grid Partly Available

Grid only partly available indication

Active Digital Input

Site_Global.Grid_Partly_Availabale

 

 

4

 

LVD  Alarm 

This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold.

At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage.

 

Active Digital Input

 

Site_Global.DC_Alarm_LVD

 

5

Consumers' load drop

If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active.

 

As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report).

Active Analog Input

Site_Global.Alarm_Consumers_Load_Drop.

 

 

 

 

6

 

 

 

 

 

 

 

No AC Load

 

 

 

 

 

 

 

No AC power to the Rectifier

Active Digital Input

 

 

 

Site layout

 

Active Digital Input
Active Digital Input
Active Analog Input

 

Active Digital Input
Active Digital Input
Active Analog Input

Site_Global.AC_Fail

||

(

Non Hybrid

&& 

(AC_Meter_ATS.Configured) && !(AC_Meter_ATS.Disconnected && (AC_Meter_ATS.I_LX=0)

||

(AC_Meter_Grid.Configured) && !(AC_Meter_Grid.Disconnected && (AC_Meter_Grid.I_LX=0)

)

 

 

 

 

 

 

 

X=1→3

7

Tenant load drop

If Colo_Meter_X.I_L1+2+3 < 50% of Colo X Average Current then the alarm active
As soon as the tenant's consumption falls below 50% of the average for the previous seven days, an alarm will be generated (the average is updated every night according to the summary report).

Active Analog Input

Tenant_X.Alarm_Load_Drop 

X=1->20

8

No  Mains

Grid is currently not available

Active Digital Input

Site_Global.Grid_Fail

 

 

9

 

PLD Alarm 

This is a DC voltage threshold - the system will trigger a Partial Load Disconnect) alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold.

At this voltage, the rectifier begins disconnecting none essential Loads to save battery energy for essential loads.

 

Active Digital Input

 

Site_Global.DC_Alarm_PLD

 

10

Power Supply Failure

No power to Galooli RTU

Active Status

External Voltage < 0.5

 

 

11

 

Grid High Voltage

Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid exceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active.

Active Digital Input

 

Gird_High_Voltage

 

12

Site on Batteries

The site is currently powered by Battery

Active Digital Input

Site_Global.Alarm_Battery_On_Load

 

13

Smart Batteries Alarm Active

At least 1 smart battery alarm is active

Active Analog Input

Smart_Battery_X.Alarms are not blank, 0 or indicator

X=1 → 14 

14

Smart Batteries Disconnected 

At least 1 of the Smart Batteries is currently not communicating with the Galooli RTU

Active Digital Input

 Smart_Battery_X.Disconnected

X=1 → 14

15

Unknown On Load

Galooli RTU can not determine the Site power source

Active Digital Input

Site_Global.Unknown_On_Load

1

Rectifier Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier

Non-Urgent

At least 1 critical mapped alarm is triggered on the rectifier

Active Digital Input

 Rectifier_X_Alarm_Non_Urgent 

X= 1 → 5

2

Battery Alarm

Rectifier's internal battery alarm

Active Digital Input

Rectifier_X.Alarm_Internal_battery

X= 1→5

3

BLV

Rectifier's internal battery low voltage alarm

Active Digital Input

Rectifier_X.Alarm_Internal_BLV

X=1 → 5

4

Critical Alarm

At least 1 critical mapped alarm is triggered on the rectifier but not internal main failure

Active Digital Input

(Rectifier_X.Alarm_Critical) && ! (Rectifier_X.Alarm_Internal_Mains_failure)

X=1 → 5

5

Disconnected

No communication between the rectifier panel and the Galooli RTU

Active Digital Input

Rectifier_X.Disconnected

X=1 → 5 

6

High Battery Temp 

Rectifier's internal High Battery Temp  alarm

Active Analog Input

 Rectifier_X.Temperature_Battery > 37

X =1 → 5

7

HW Failure

Rectifier's internal HW Failure alarm

Active Analog Input

Rectifier_X.alarm_Internal_HW_failure

X =1 → 5

8

Load Breaker

Rectifier's internal Load Breaker alarm

Active Analog Input

Rectifier_X.Alarm_Internal_Load_Breaker

X =1 → 5

9

LVD

Rectifier's internal Low Voltage Disconnect alarm

Active Analog Input

Rectifier_X.Alarm_Internal_LVD

X =1 → 5

10

Mains Failure

Rectifier's internal Mains Failure alarm

Active Analog Input

Rectifier_X.Alarm_Internal_Mains_failure

X =1 → 5

11

MCB

Rectifier's internal Master Circuit Braker alarm

Active Analog Input

Rectifier_X.Alarm_Internal_MCB_Fail

X =1 → 5

 

12

 

Modules Fault

 

At least one of the available Rectifier modules is not working

 

Active Digital Input

Rectifier_X.Alarm_Internal_Urgent_RFA

||

Rectifier_X.Alarm_Internal_NonUrgent_RFA

 

X =1 → 5

13

Non-Urgent RFA

Rectifier's internal Non Urgent Recetifier Fault alarm

Active Digital Input

Rectifier_X.Alarm_Internal_NonUrgent_RFA

X =1 → 5

14

OVP

Rectifier's internal Over Power alarm

Active Digital Input

Rectifier_X.Alarm_Internal_OVP

X =1 → 5

15

PLD

Rectifier's internal Priority Low Deffered alarm

Active Digital Input

Rectifier_X.Alarm_Internal_PLD

X =1 → 5

16

Rectifier X Door 

At least 1 of the Rectifier Cabinet door is opened

 Active Digital Input

  Rectifier_X.Alarm__Door

X=1 → 5

17

Temp High

Rectifier's internal Temp High alarm

Active Digital Input

Rectifier_X.Alarm_Internal_Temperature

X =1 → 5

18

Urgent Alarm

At least 1 critical mapped alarm is triggered on the rectifier

Active Digital Input

 Rectifier_X_Alarm_Urgent

X=1 → 5 

19

Urgent RFA

Rectifier's internal failure alarm

Active Digital Input

Rectifier_X.Alarm_Internal_Urgent_RFA

X=1 → 5

20

Urgent PFA

Rectifier's internal failure alarm

Active Digital Input

Rectifier_X.Alarm_Internal_Urgent_PFA

X=1 → 5

21

Non Urgent PFA

Rectifier's internal failure alarm

Active Digital Input

Rectifier_X.Alarm_Internal_Non_Urgent_PFA

X=1 → 5

Inverter Alarms

 

Alarm Number

Alarm Type

Alarm Name

Description

Parameter Type

System Parameter Name

Index

1

Inverter

solar alarm

If any of the inverter's solar alarms are true, the alarm is on

Active Digital Input

Inverter_X.Solar_Y_Alarm_Active

 X = 1 → 15

Y = 1 → 4