Group: Collo Meter X
Field Name | Field Meaning and Logic |
---|---|
      Alarm_Load_Drop | If Colo_Meter_X.I_L1+2+3 < 50% of Colo X Average Current then the alarm active These alerts are activated when the site/tenant's consumption falls below 50% of the average for the previous seven days (the average is updated every night according to the summary report). Where the tenants have relocated or used more than one meter per tenant, the average is calculated according to the tenant, not the power meter, so:
|
Alarm Power Down | In layouts that will be defined as microgrids, the alarms will not be active. When there is no continuous consumption of current at a site, there is no need to alert that there is no load. |
Alarm Load Down | |
 Power | This is the direct reading of the power value from the Tenant DC meter, or a calculation based on the voltage, current and PF read from the Tenant DC meter. |
 PF L1-3 (Power Factor) | The Power Factor (PF) reading from the Tenant DC meter. The Power Factor will be filled with a default value of 0.95 if there is no power factor for the phase and no direct reading of power, voltage, and current (all three). |