Galooli Solution Version - July 6, 2025
The latest version of the Galooli solution incorporates features that reflect our open dialogue with our customers and Galooli's desire to facilitate and improve the system's use. The purpose of this article is to provide information about the main features of this version.
Panorama Application
Battery Autonomy Display
Battery Autonomy represents the amount of time a site’s smart batteries can continue supplying power without external energy sources (i.e., without charging).
This feature helps customers plan site energy reserves for critical scenarios such as power grid outages, generator failures, and more.
It also enables customers to identify cases of poor energy planning where unnecessary generator or grid usage could have been avoided by leveraging the available battery capacity—reducing both costs and carbon emissions.
When is it displayed?
When the following conditions are met:smart_battery_x.configured = True
site_global.battery_discharging = False
The Battery Autonomy value will be visible in Panorama Live in the following locations:
Main Site Status Card
Site Status Sub-Card
Table Mode → Site Global → Smart Battery Autonomy
How is it calculated?
The general formula is:
Available SOC × Available Capacity ÷ Site Load
Each element of the formula is calculated individually, considering various battery types and configurations.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2891251716/Site+Status+Card#Battery-Autonomy
Request Location Cooldown
We deployed a cooldown mechanism for “Request Location” actions (Panorama Live).
The mechanism prevents users from sending more than one request every 30 seconds.
Rear More - https://galooli.atlassian.net/wiki/x/BABVr
Rectifier Card - 20 Modules Supported
The system now supports the display of up to 20 modules per rectifier (previously limited to 12).
Read More - https://galooli.atlassian.net/wiki/x/AYBcr
X-Ray Tab - "Configuration" Parameter Removed
The Configuration field was removed from the Panorama Live – X-Ray view, as the relevant information now appears at the top of each section.
Read More - https://galooli.atlassian.net/wiki/x/AQB25Q
Pro Application
Restricted Parameters
A new feature simplifies report building by displaying fields based on the user's permission level to the Pro Application, ensuring a clearer and more user-friendly experience. The feature includes updated viewing permissions for users, along with new visual indicators for the restricted fields.
Galooli maintains an internal list of fields that are restricted to users with Edit or Full permission levels in the Pro Application. Users with Read Only permission will not be able to view these fields.
Users with Edit/Full permissions will see a unique indication marking these restricted fields, which only they can access.
Read More:
Report List and List of Available Fields | Limited View (Restricted Fields)
Permission Management | Galooli Pro Permission
New Fields
Generator X Alarm Internal Oil Temperature - This field indicates whether the internal oil temperature of the generator has exceeded a critical threshold that could damage the engine or reduce performance.
Generator X.Galooli Operational Fuel - This field returns the result of the following calculation:
Galooli Engine Hours × Galooli Operational Fuel Consumption.Rectifier X.AC Meter Input Configured - Indicates whether an rectifier AC meter is configured.
Rectifier X.AC Meter Input Disconnected - Indicates whether the configured rectifier AC meter is currently disconnected.
Rectifiers Assignment Rectifiers X - This field displays the assigned custom name for each rectifier.
Read More - https://galooli.atlassian.net/wiki/x/BACSuw / https://galooli.atlassian.net/wiki/x/qADUng / https://galooli.atlassian.net/wiki/x/CQD8u
Manager Application
Device Configuration Sections Changes
The “Shelter” and “Rectifier” sections have been separated.
The “Rectifier” section was renamed to “Dry Contact Rectifier” and now includes the relevant rows previously under the “Shelters” section.
Support is now limited to one rectifier for dry contacts.
In addition, several display changes were implemented.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2830402016/Device+Configuration#Configuration-Section
New Additional Info Fields
The fields Rectifier 1–5 have been added to the Additional Info section.
These fields allow assigning a custom name to each rectifier and are located under the Rectifiers category, in the Assignment section.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2830041108/Information#Additional-Information
New Device Type
A new unit type — Router_Device — was added to the system (My Units > Information > Unit > Section Hardware). In these units, the “Unit Version” field stores the router’s IP address in Galooli cloud (which may change when it disconnects and reconnects), enabling remote access and other operations.
Show\Hide IOs on Live Display
We’ve added support for controlling the display of IOs in the Galooli Mobile Application.
Until now, the checkbox in the IO configuration popup only affected the Panorama display.
Now, it controls visibility in both Panorama and Mobile App.
Additionally, the checkbox label has been changed to Show in Live Display.
Read More - https://galooli.atlassian.net/wiki/x/doG0q
My NOC - Activation/Release Delay Default Values
We’ve applied specific Activation/Release Delay settings for the following NOC alarms:
Location – Geofence Enter
Location – Geofence Leave
Fuel Drop
The defined values are:
Activation Delay: Default is 0 and cannot be changed
Release Delay: Minimum 60 minutes
Note: Existing alarms from the list above will not be overwritten. However, if edited, the system will require applying the new settings.
Read More - https://galooli.atlassian.net/wiki/x/EYBH8Q
Preferences “Read Only” Permissions Display
In the upcoming version, the display in the Preferences tool within the Manager application will be updated for users with Read Only permissions.
Instead of dimming the entire screen, only the editable fields will be disabled, improving readability and overall user experience. No changes were made for other permission types in this module.
Read More - https://galooli.atlassian.net/wiki/x/aQBbmQ
Users Configuration Expiration & Last Activity Filters
We’ve updated the filter values for the Expiration Time and Last Activity fields to align with the table view. Previously, the filters displayed the exact number of days, which made them difficult to use effectively.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2580447265
Geofences Report - Removed Fields
We've removed irrelevant fields from the Geofences Report (generated from the My Geofences menu in the Manager application).
The following fields were removed:
Group ID
Parent ID
ID
Server Update Time
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2581528581
NOC Application
NOC Dashboard New Fields
We added the Cluster Name and Group Name fields to the report that serves as the data source for the NOC dashboard.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2483945485/Galooli+NOC+Application#NOC-Dashboard
NOC Live Data Menu Improvements+
We improved the Live Menu mechanism in the NOC Application to support all unit types in the system.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/2483945485/Galooli+NOC+Application#Live-Data
General Updates
Free-Cooling (Power Center)
This feature allows defining automation rules for the Free-Cooling module, designed to reduce energy consumption by using cool outdoor air to ventilate indoor spaces instead of running the air conditioner.
New Alarms
Generator_X.Alarm Internal Oil Temperature. Criticality level: Urgent
Rectifier X AC Meter Input Configured
Rectifier X AC Meter Input Disconnected
Organizational Tree Arrows Behavior
Starting from the upcoming version, it will be possible to navigate the organizational tree using the keyboard arrow keys.
Navigation will be available only after initially selecting an object in the tree with the mouse.
Up/Down – Navigate between objects in the tree
Right/Left – Expand/Collapse Organization / Cluster / Group objects
Enter – Select the currently highlighted object
SDK Fields Modifications
As part of our continuous improvement efforts, several SDK field names have been updated to align with current standards and functionality. Please review and update your SDK queries to reflect these changes. A detailed list of the updated field names is available at the following link.
As of June 1, 2025, queries using the old field names will no longer be supported.
New Knowledge Base Documents
Galooli Data Deletion Procedure - This document outlines Galooli's official procedure for processing client-initiated data deletion requests - https://galooli.atlassian.net/wiki/spaces/KP/pages/4324229324
New FAQ Article - https://galooli.atlassian.net/wiki/spaces/KP/pages/4339367971
New Hardware Support and Integrations
#Hardware
New flow meter integration - Pulita Energy YLG10 (requires Elara Gateway version 02.02.55) - https://galooli.atlassian.net/wiki/x/AYBKAAE
New USR data logger models support - https://galooli.atlassian.net/wiki/x/AQBk-g
New Generator Controller support - https://galooli.atlassian.net/wiki/x/AYABAQE
New Shoto Smart Battery support - SDA10 Black - https://galooli.atlassian.net/wiki/x/AQDd9g
New Delta Huawei Smart Battery support - https://galooli.atlassian.net/wiki/spaces/KP/pages/3886809091/Delta+Rectifier+Supported+Smart+Batteries#Delta-Huawei
New Eltek Smart Battery Support - https://galooli.atlassian.net/wiki/x/AYClAwE
New Rectifier Model - Benning MCU3000 - https://galooli.atlassian.net/wiki/x/AYCY-g
New Network Camera - https://galooli.atlassian.net/wiki/spaces/KP/pages/4340219905
New AC Meter model support - https://galooli.atlassian.net/wiki/x/AQA1qg (DRT-341C)
Ultragate Internal IO’s Configuration
A new feature has been introduced allowing mixed analog input configurations. Users can now set specific inputs to measure either voltage or current independently. For example, Inputs 1, 2, and 4 can be configured to measure voltage, while Input 3 is set to measure current.
To enable this functionality, the corresponding “Address” values must be updated accordingly.
Read More - https://galooli.atlassian.net/wiki/spaces/KP/pages/3604217863/Ultragate+Installation+Configuration#Internal-IO%E2%80%99s-Configuration
Products End Of Sale Dates
K3 End of Life - June 29th, 2025