CE Transducer CE11
The DC Meter is a split-core current measurement of DC power.
DC Multi-parameter monitoring, U, I, P, KWH
Various models for various measure range for option:
Current: 0-500A~300ADC (100A & 500A)
Voltage: 0-1000V (60V & 1000V)
Energy data power failure protection
Bi-direction detection for U, I, P, KWH
Work with a wide range of power sources, +9V~+24V
High stability, 2KV surge protection on input, power supply, and output interface
Technical Specification | |
Temperature Range (operating) | -10°C – +5°C |
Measuring range | 0~50-500ADC, 0-1000VDC |
Baud rate | 19200, 9600(default), 4800, 2400, 1200 |
Isolation voltage | 2500 V DC |
Temperature drift | ≤1000ppm/°C |
Output | DC voltage, DC current, DC power and energy |
Meter voltage reading accuracy (Same for both transducers) | ±0.2% |
Meter current reading accuracy | ±1% |
Overall kwh accuracy | ±1.20% |
   Standards and Certifications |
|
Technical Specifications
Manufacturer's website - SSET
Model | Manufacturer PN. | Galooli PN. | Manufacturer Datasheet |
---|---|---|---|
Energy DC Meter CE11 60V*100A | CE-AD11B-34GS4-1.0/60V*100A | 400-DCMultMtr-516 (Old Version) | Â Â |
Energy DC Meter CE11 60V*100A | CE-AD11D-34GS4-1.0/60V*100A | 401-DCMultMtr-516 (New Version) | |
Energy DC Meter CE11 60V*500A | CE-AD11D-34GS4-1.0/60V*500A | 401-DCMultMtr-500A | |
Energy DC Meter CE11 1000V*100A | CE-AD11B-34GS4-1.0/1000V*100A | 400-DCMultMtrHigh-516 |
Test Report
Pinout Diagram
Pin# | Name |
---|---|
1 | Voltage measure (+) |
4 | Voltage measure (-) |
5 | POWER (12V) |
6 | GND (-12V) |
8 | RS485 B |
9 | RS485 A |
Â