Relay & Socket
Relays are electromechanical switches that open and close electrical circuits.
By using Galooli Gateways and the appropriate relay, you will be able to gain valuable data about the equipment on site. Relay is commonly used for the following purposes:
An indication of the generator's operation status
An indication of the status of the grid phases
Status of the AC/DC tower lighting
Control the generator remotely
The Relay is comprised of two parts:
The Coil Relay
The Terminal Bridge
AC Relay & Socket
Features
Voltage - 110V / 220V
High contact current (16A)
5kV dielectric strength (Coil to Contacts)
UL Isolation Class F
Supported Models
Product Name | Galooli PN. |
AC Relay & socket 110V | 400-Relay110V-33 |
AC Relay & Socket 220V | 400-KRT424730-33 |
Technical Specification
Parameter | Specification |
|---|---|
Product Type | Power Relay (HF115F-A series) |
Coil Voltage | 24 VAC / 115 VAC / 230 VAC |
Contact Arrangement | 1 Form A, 1 Form B, 1 Form C / 2 Form A, 2 Form B, 2 Form C |
Contact Rating | Up to 16 A (depending on version) |
Contact Material | AgSnO₂, AgNi, AgSnO₂+Au plated (options) |
Insulation Class | Class F |
Construction | Plastic sealed / Flux-proof |
Operating Temperature | –40 °C to +85 °C |
Dielectric Strength | Meets IEC standards |
Mounting | PCB mounting |
Compliance | IEC / EN 61810 |
Relay & Socket Installation and Configuration For Generator Status and Controlling
Relay & Socket Installation and Configuration For Generator Status and Controlling
Manufacturer Data
DC Relay & Socket
Features
Voltage - 12V / 24V / 48V
High contact current (16A)
Low height (15.7mm)
5kV dielectric strength (Coil to Contacts)
UL Isolation Class F
Supported Models
Product Name | Galooli PN. |
|---|---|
DC Relay & Socket 12V | 400-Relay12V-33 |
DC Relay & Socket 24V | 400-Relay24V-33 |
DC Relay & Socket 48V | 400-Relay48V-33 |
Technical Specification
Parameter | Specification |
|---|---|
Product Type | Miniature High Power Relay |
Coil Voltage | 5, 6, 9, 12, 18, 24, 48 VDC |
Contact Arrangement | 1 Form A / 1 Form C / 2 Form A / 2 Form C |
Contact Rating | Up to 16 A (model-dependent) |
Max Switching Voltage | 400 VAC |
Max Switching Power | Up to 4000 VA |
Contact Resistance | ≤ 100 mΩ (at 1A, 6VDC) |
Contact Material | AgSnO₂ / AgNi |
Dielectric Strength | 5 kV (between coil & contacts) |
Insulation Resistance | ≥ 1000 MΩ (at 500 VDC) |
Operate Time | ≤ 10 ms |
Release Time | ≤ 5 ms |
Operating Temperature | –40 °C to +85 °C |
Mounting | PCB |
Construction | Flux-proof / Plastic sealed |
Compliance | IEC 60335-1, UL, VDE, RoHS |
Relay & Socket Installation and Configuration For Generator Status and Controlling
Relay & Socket Installation and Configuration For Generator Status and Controlling
Manufacturer Data
Relay Socket
Product Name | Manufacturer PN. |
Screw press wire frame Relay Socket. | 14FF-2Z-C2-3 |
Pinout Diagram
Pin # | Pole | Description |
|---|---|---|
A1 & A2 | X | Coil |
11 | POLE 1 | COMMON |
12 | POLE 1 | NORMALLY CLOSE |
14 | POLE 1 | NORMALLY OPEN |
21 | POLE 2 | COMMON |
22 | POLE 2 | NORMALLY CLOSE |
24 | POLE 2 | NORMALLY OPEN |