Smoke Detection Sensor

The smoke detector’s purpose is to monitor any presence of smoke/fire.

Features

  • Monitors for the presence of smoke and/or fire and gives off an alarm when detected

  • External power

  • Indoor use only

Technical Specification

Diameter

101 mm including base

Height (including base and LED)

52 mm

Weight

106 gr.

Operating Temperature Range

-10°C - +60°C (14°F - 140°F)

Relative Humidity Range

10% - 93% non-condensing

Sensitivity Range

1.8%±0.5% / foot obscuration

Operating Voltage (supplied by control panel via SLC)

12-28 Vdc

 

 

 

Standards and Certifications

  • CE Marking

  • UL 268

  • EN 54-7

  • RoHS Compliance

  • ISO 9001

  • EN 50130-4

  • EN 61000-6-2

  • FCC Part 15 (if applicable)

Additional Information

  • Manufacturer PN. - TFB-180RL + TFO-480

  • Galooli PN. - 400-SmokeT440-843

  • Manufacturer datasheet

Pinout Diagram

This pinout refers to the smoke sensor, which operates in a Normally Closed (NC) configuration.

Pin #

Name

Default Cable Color

Pin #

Name

Default Cable Color

1

Smoke sensor GND

No default color (Blue in the image bellow)

2

Smoke sensor Power (+12V)

No default color (Pink in the image bellow)

3

Relay Power (+V)
Connected by default

Red (default)

4

Relay Power (-V)

Connected by default

Black (default)

NO

Normally Open (NO) Communication

Disconnected by default

Green (default)

COM

Common Terminal (COM)

Connected to pin 2 by default

White (default)

NC

Normally Closed (NC) Communication

Connected by default

Yellow (default)

image-20241128-084411.png

Installation Process

  1. Connect the power source to the smoke sensor according to the image above (Pins 1 and 2)

  2. Ensure the relay is connected to the power source (pins 3 and 4).

  3. Leave the NO communication cable disconnected (Green)

  4. Make sure the COM cable (White) is connected to a positive power source (pin 2) to enable the sensor's NC mode.

  5. Connect the NC (Yellow) communication cable to the Galooli gateway.

The installation instructions and image above are for configuring the alarm to be active in the system when the voltage is 0V and inactive when the voltage is 12V.

For reverse logic, where the alarm is active at 12V, connect the COM (white cable) to GND (pin #1).