Leoch Batteries

Leoch Batteries

image-20250408-123209.png
Averge Technologies is a subsidiary under Leoch International

Supported Model

100Ah

Communication Method

RS485 (Modbus)

Pinout/Wiring Diagram

Pin 1 : RS485 B− (T/R−)

Pin 2 : RS485 A+ (T/R+)

Pin 3 : GND

Pin 4 : Reserved

Pin 5 : Reserved

Pin 6 : GND

Pin 7 : RS485 A+ (T/R+)

Pin 8 : RS485 B− (T/R−)

image-20250408-114759.png

Pin 1 : RS485 B− (T/R−)

Pin 2 : RS485 A+ (T/R+)

Pin 3 : GND

Pin 4 : Reserved

Pin 5 : Reserved

Pin 6 : GND

Pin 7 : RS485 A+ (T/R+)

Pin 8 : RS485 B− (T/R−)

image-20250408-114759.png

Physical Installation

Connect an Ethernet LAN cable from the Galooli Gateway/Computer to the RS485 A port on the left side of the first battery. Ensure that the right-side RS485 port is used to connect the first battery to the left-side RS485 port of the second battery. Continue this daisy-chain connection for all additional batteries.

It is recommended, whenever possible, to connect the smart batteries to RS485 Port 2, separately from other RS485-connected devices and sensors such as fuel sensors, power meters, etc. This approach enhances surge protection for the batteries and isolates them from potential surges affecting the other RS485-connected devices.

image-20250408-122246.png

Device Configuration

If you, as a user, wish to view the battery data directly through the battery’s own portal and compare it with the values shown in Power Center, follow these steps:

Download and open the “PbmsTools V2.4 file”. Extract the file and run the “Pbms tool”. Below display will be shown, select the serial port for your laptop, open the port.

image-20250408-115150.png

For configuring the physical ID when there are one or more batteries connected to one another, the following actions must be taken. As shown in the table, the "ADD" part must be configured according to the number of batteries, on each battery separately.

image-20250421-104915.png

Power Center Configuration

image-20250115-111930.png

ID assignments:

Battery

Physical ID

Virtual ID

Baudrate

1

1

70

19200

2

2

71

19200

3

3

72

19200

4

4

73

19200

5

5

74

19200

Supported Parameters

Power Center Parameters

System Parameters

Remarks

Power Center Parameters

System Parameters

Remarks

Voltage

Smart_Battery_X.Voltage [V]

 

Current

Smart_Battery_X.Current [A]

 

Temperature_Ambient

TBA

 

 

 

Temperature_1-2

 

 

Smart_Battery_X.Temperature_X[Celsius]

Temperature 1 - cell temperature

Temperature 2 - cell temperature

Since lithium batteries are prone to catching fire and exploding at high temperatures, there are two temperature meters for the same purpose.

Battery_SOH

Smart_Battery_X.SOH

 

Battery_SOC_Percentage

Smart_Battery_X.SOC

 

Battery_Cycles

Smart_Battery_X.Cycles

 

Alarms List

TBA

Manufacturer Data

TBA