RPT Power Batteries

RPT Power Batteries

Supported Models

NMC48235

Communication Method

RS485 (Modbus)

Wiring Diagram

Pinout

RJ45 side ports

1 or 8

RS485 B

2 or 7

RS485 A

Physical Installation

Connect an Ethernet LAN cable from the Galooli Gateway/Computer to the RS485 A port on the left side of the first battery. Ensure that the right-side RS485 port is used to connect the first battery to the left-side RS485 port of the second battery. Continue this daisy-chain connection for all additional batteries.

It is recommended, whenever possible, to connect the smart batteries to RS485 Port 2, separately from other RS485-connected devices and sensors such as fuel sensors, power meters, etc. This approach enhances surge protection for the batteries and isolates them from potential surges affecting the other RS485-connected devices.

image-20250318-081034.png

Device Configuration

For configuring the physical ID when there are one or more batteries connected to one another, the following actions must be taken. As shown in the table, the "ADD" part must be configured according to the number of batteries, on each battery separately.

image-20250318-080441.png
image-20241028-100701.png

Power Center Configuration

image-20250115-111321.png

Supported Parameters

Power Center Parameters

System Parameters

Remarks

Power Center Parameters

System Parameters

Remarks

TBA

 

 

Alarms List

Critical

Urgent

Critical

Urgent

"Monomer Over Voltage protection"

"Temp1"

"Monomer Over Discharge protection"

"Temp2"

"Total Voltage Over Voltage protection"

"Temp3"

"Total Voltage Over Discharge protection"

"Temp4"

"Charging Over Current protection"

"Temp5"

"Discharge Over Current protection"

"Pack Charge Current"

"Short Circuit"

"Pack Voltage"

"High Temperature Protection for Charging"

"Pack Discharge Current"

"Discharge High Temperature protection"

"CFET indication"

"Charge Low Temperature protection"

"DFET indication"

"Discharge Low Temperature protection"

"Use Pack Power Support indication"

"Charge MOS fault"

"Charger Reverse Connection indication"

"Discharge MOS fault"

"ACin"

"Faulty Temperature Sensor"

"Heated film indication"

"Power Supply failure"

"High Temperature alarm during charging"

"Battry Cell is faulty"

"Discharge High Temperature alarm"

"Sampling falure"

"Charging Low Temperature alarm"

"Precharge failure"

"Discharge Low Temperature alarm"

"Mnoblock Overvoltage alarm"

"High Ambient Temperature alarm"

"Monoblock low pressure alarm"

"Low Ambient Temperature alarm"

"Total voltage Overvoltage alarm"

"MOS High Temperature alarm"

"Total Pressure Low Pressure alarm"

"Low Battery alarm"

"Churging Overcurrent alarm"

 

"Discharge Overcurrent alarm"

 

Manufacturer Data