Air Condition AC On/Off Current Sensor

Air Condition AC On/Off Current Sensor

Air Condition (A/C) ring sensors are used to detect loads going to the air conditioner and provide the status of the air conditioner.

 

Features

Self-powered, AC current sensing device, providing on/off status of electric loads including fans, pumps, motors, heaters, and virtually any AC powered device.

  • Low turn-on (less than 0.150 A)

  • Hysteresis and anti-transient circuitry eliminates chatter and false switching

  • Easy Wiring

  • Rugged enclosure

Supported Models & Communication Methods

Model

Galooli PN.

Elkor i-Snail-S

400-ACCurStaD-036

Technical Specification

Power

Self Powered from the monitored line.

Current Input

0.150 to 100A

 

Output

Bi-directional, normally open relay.
4 ohms MAX when closed.
40V (AC/DC) @ 200mA

Switch Point

≤ 150mA

Hysteresis

~10mA (ie: on at 150mA, off at 140mA)

Enclosure

ABS (UL 94V-0) Plastic box 2"x1.6"x0.9"

Weight

2.4 oz (68 g)

Wire Window

0.54" (13.7 mm)

Terminal Block (-S)

Barrier Strip. Accepts up to 12-26AWG

Lead Length (-S-w)

6" (15 cm)

 

 

Standards and Certifications

  • CE Marking

  • UL

  • IEC 61010-1

  • IEC 61869-2

  • RoHS Compliance

  • ISO 900

  • EN 61000-6-2/4

Wiring/Pinout Diagram

To be released

Physical Installation

To be released

Manufacturer Data