Vertiv

  • Supported Models

    Vertiv M530B

Device IP

 192.168.1.2

Subnet mask

 255.255.255.0

Gateway

 192.168.1.1

Host IP (Web/Elara configuration)

 192.168.1.5

Vertiv M820D_ ACU_ PLUS

Vertiv M830B_ NCU

Device IP

10.1.1.102

Subnet mask

255.255.255.0

Gateway

10.1.1.1

Host IP (Web/Elara configuration)

10.1.1.103

  • Communication Method
    ETHERNET/SNMP

  • Read/Write Community

    • Vertiv M530B:
      Read - public
      Write - (keep it empty)

    • Vertiv M820D_ ACU_ PLUS / Vertiv M830D_ NCU:

      Read - public
      Write - public

  • Device Configuration
    To be announced

Supported Parameters (SNMP)

  • M530B

Power Center Parameters

System Parameters

Remarks

Power Center Parameters

System Parameters

Remarks

Total_Output_KWH

Rectifier_X.Total Load Energy [KWH]

 

Voltage

Rectifier_X.U_System [V]

 

Current

Rectifier_X.I_Load

 

Battery_Current

Rectifier_X.I_Rectifier

 

Battery_SOC_Percentage

Rectifier_X.State_Of_Charge

 

Internal_Temperature

Rectifier_X.Temperature_Internal [Celsius]

 

Battery_Temperature

Rectifier_X.Temperature_Battery [Celsius]

 

Solar_W

Rectifier_X.Solar_Power [W]

 

Solar_KWH

Rectifier_X.Solar_Total_Power [KWH]

 

Solar_Curent

Rectifier_X.Solar_Current [A]

 

Comunication_Modules

Rectifier_X.Communication_Rectifier_Modules

 

Comunication_Solar_Modules

Rectifier_X.Communication_Solar_Modules

 

Load_Used_Capacity

Rectifier_X.Used_Capacity

 

  • M820D_ ACU_ PLUS

Power Center Parameters

System Parameters

Remarks

Power Center Parameters

System Parameters

Remarks

Grid_Voltage_Phase_1-3

TBA

 

Voltage

Rectifier_X.U_System [V]

 

Current

Rectifier_X.I_Load

 

Battery_Current

Rectifier_X.I_Rectifier

 

Battery_Temperature

Rectifier_X.Temperature_Battery [Celsius]

 

Temperature 2

Rectifier_x.Module_Temperature_x [Celsius]

 

Battery_SOC_Percentage

Rectifier_X.State_Of_Charge

 

Load_Used_Capacity

Rectifier_X.Used_Capacity

 

  • M830D_ NCU

Power Center Parameters

System Parameters

Remarks

Power Center Parameters

System Parameters

Remarks

Total_Output_KWH

Rectifier_X.Total Load Energy [KWH]

 

Voltage

Rectifier_X.U_System [V]

 

Current

Rectifier_X.I_Load

 

Battery_Current

Rectifier_X.I_Rectifier

 

Battery_Temperature

Rectifier_X.Temperature_Battery [Celsius]

 

Battery_SOC_Percentage

Rectifier_X.State_Of_Charge

 

Solar_KWH

Rectifier_X.Solar_Total_Power [KWH]

 

Solar_W

Rectifier_X.Solar_Power [W]

 

Temperature 2

Rectifier_x.Module_Temperature_x [Celsius]

 

Solar_1-8_Voltage

Rectifier_X.Solar_Voltage_X [V]

 

Solar_1-8_Current

Rectifier_X.Solar_Current_X [A]

 

Grid_Voltage_Phase_1-3

TBA

 

Comunication_Modules

Rectifier_X.Communication_Rectifier_Modules

 

Comunication_Solar_Modules

Rectifier_X.Communication_Solar_Modules

 

Load_Used_Capacity

Rectifier_X.Used_Capacity

Â