eSite
Supported Models
eSiteCommunication Method
ETHERNET/SNMP
RS485 (This connection method is not recommended, but if necessary, contact Galooli support)Read/Write Community
Read - public
Write - esitex10Network configuration
Device IP | 192.168.20.10 |
---|---|
Subnet mask | Â 255.255.255.0 |
Gateway | Â 192.168.20.1 |
Host IP (Web/Elara configuration) | Â 192.168.20.11 |
Device Configuration
To be announced
Supported Parameters (SNMP)
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Total_Output_KWH | Rectifier_X.Total Load Energy [KWH] | Â |
Voltage | Rectifier_X.U_System [V] | Â |
Current | Rectifier_X.I_Load | Â |
Battery_Current | Rectifier_X.I_Battery | Â |
Battery_SOC_Percentage | Rectifier_X.State_Of_Charge | Â |
Battery_Temperature | Rectifier_X.Temperature_Battery [Celsius] | Â |
Solar_W | Rectifier_X.Solar_Power [W] | Â |
Solar_KWH | Rectifier_X.Solar_Total_Power [KWH] | Â |
Rectifier_Current | Rectifier_X.I_Rectifier | Â |
Temperature_Ambient | Rectifier_X.Temperature_Ambient [Celsius] | Â |
Solar_1-6_Voltage | Rectifier_X.Solar_Voltage_X [V] |
 |
Solar_1-6_Current | Rectifier_X.Solar_Current_X [A] | |
Grid_Voltage_Phase_1-3 | TBA | Â |
DG_Signal | Rectifier_X.Generator Signal | Â |
Communicating_Modules | Rectifier_X.Communication_Rectifier_Modules | Â |
Communicating_Solar_Modules | Rectifier_X.Communication_Solar_Modules | Â |