Cooling Control System (Supported Product)

A control unit for the cooling system.

It is composed of two main types of units: a transfer switch and a central control unit (CCU).

Transfer switches are connected to individual cooling units (up to 40 units) and all transfer switches are connected to one central cooling unit (up to 4 units).

A central control unit (CCU) is connected to the Elara gateway.

The following parameters are supported by Galooli:

Digital/Analog Parameters

Cooling units/Air conditioners

Central Control Unit (CCU)

Digital/Analog Parameters

Cooling units/Air conditioners

Central Control Unit (CCU)

 

Digital

  • Configuration Status (True or False)

  • Unit Disconnected Status (True or False)

  • Unit On Status (True or False)

  • Configuration Status (True or False)

  • Unit Disconnected Status (True or False)

  • System Alarm (Critical/Urgent/Non Urgent - True or False)

 

Analog

  • Room temperature

  • Power (W)

  • Device Type

  • System Temperature (the average temperature of all air conditioners connected to this controller)

Supported Models

Communication Methods

Supported Models

Communication Methods

Coolsure CCU 06

ETHERNET/Modbus Over TCP

  • Network configuration for ETHERNET/Modbus Over TCP connection

Device IP

192.168.100.103

Device IP

192.168.100.103

Subnet mask

255.255.255.0

Gateway

192.168.100.1

Host IP (Web/Elara configuration)

192.168.100.101

  • ETHERNET/Modbus Over TCP Configuration

  • Power Center Configuration
    Default data for Coolsure cooling system units.

    • Cooling system 1 id = 241

    • Cooling system 2 id = 242

    • Cooling system 3 id = 243

    • Cooling system 4 id = 244

Â