Polarium Batteries
Supported Models
Polarium
Communication Method
RS485 (Modbus)
Wiring Diagram
Pinout | RJ45 bottom side ports | |
4 | RS485 A | |
5 | RS485 B | |
6 | RS485 GND |
Physical Installation
The Module ID is automatically assigned by the master module in sequential order from 1 to N, based on the configured device count.
Polarium batteries support up to 14 batteries connected to a single Battery Management System (BMS) as the master battery. Galooli's solution is compatible with this configuration, supporting the connection of 14 batteries via a single Galooli gateway.
Device Configuration
Download the “Incell Studio Platform”.
Open the file and follow the instructions.
Version Update
Polarium batteries can be updated using a specific mechanism built as a service. As a result, we are able to remotely connect to Polarium batteries and update them with the latest version.
Please contact the Galooli support team for more information.
Power Center Configuration
Alarms List
Critical | Non Urgent | Observation |
---|---|---|
"Circuit breaker alarm" | "CLD active indicator" | "Charge stop indicator", |
"Anti-theft alarm" |
| "Balanced cells indicator" |
"Short-circuit alarm" |
| "Non-quiescent state indicator" |
"Over-current discharge alarm" |
| "Charge stop ready indicator" |
"Over-temperature alarm" |
|
|
"Under-voltage alarm" |
|
|
"Over-voltage alarm" |
|
|
"Discharge blocked alarm" |
|
|
"Under-temperature alarm" |
|
|
"Over-current charge alarm" |
|
|
"Charge blocked alarm" |
|
|
Supported Parameters
Power Center Parameters | System Parameters | Remarks |
---|---|---|
Battery SOC Percentage | Smart_Battery_X.SOC |
|
Battery SOH | Smart_Battery_X.SOH |
|
Voltage | Smart_Battery_X.Voltage [V] |
|
Current | Smart_Battery_X.Current [A] |
|
Cell Voltage Min | Smart_Battery_X.Cell_Voltage_Min [V] |
|
Cell Voltage Max | Smart_Battery_X.Cell_Voltage_Max [V] |
|
Temperature 1-3 |
Smart_Battery_X.Temperature_1-3 [Celsius] | Temperature 1 - cell temperature Temperature 2 - cell temperature Since lithium batteries are prone to catching fire and exploding at high temperatures, there are two temperature meters for the same purpose. Temperature 3 - FET temperature |
Battery Cycles | Smart_Battery_X.Cycles |
|
Manufacturer Data
Troubleshooting
Communication Troubleshooting
How to Detect the Fault? | Troubleshooting Steps
|
---|---|
Polarium battery connection state is "No Connection", even though the battery is connected.
| Verify that the baud rate of the Polarium is the same as the baud rate of all devices and the Elara gateway.
|