ACREL AMC16 DETT

channels DC energy meter (With External DC Current Hall sensor)

Technical Specification

Voltage range

-40V~-60VDC 

Hall sensor power supply

Power supply output:+12V/100Ma, -12V/50mA

Communication

Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps.

 

 

 

Standards and Certifications

  • CE Marking

  • IEC 61010-1

  • IEC 61000

  • IEC 60068

  • ISO 9001

  • MID (If applicable, for energy metering in the EU)

  • RoHS Compliance

  • UL Certification (if applicable, for North America)

  • RS485 Protocol Compliance

Technical Specifications

  • Manufacturer's website - Acrel Electric

  • Manufacturer PN. - AMC16-DETT

  • Galooli PN. - 400-DCMeterAcr-516

  • Manufacturer datasheet

Pinout Diagram

 

Pin number

Description

Pin number

Description

1

Power Supply +

2

Power Supply -

30

RS485 - A 

31

RS485 - B 

10

Input voltage + (common for all channels)

11

Input voltage - (common for all channels)

37

Power Supply to Hall Sensors (+12V)

38

Power Supply to Hall Sensors (G)

39

Power Supply to Hall Sensors (-12V)

4

Channel 1 (I+)

5

Channel 1 (I-)

6

Channel 2 (I+)

7

Channel 2 (I-)

8

Channel 3 (I+)

9

Channel 3 (I-)

14

Channel 4 (I+)

15

Channel 4 (I-)

16

Channel 5 (I+)

17

Channel 5 (I-)

18

Channel 6 (I+)

19

Channel 6 (I-)

 

Installation and Configuration

 

Recommended Configuration For Galooli Gateways

  • Recommended Galooli gateways:

Elara

Corona

  • Power Center recommended configuration