EX20 Modbus Temperature Configuration
Ex20 input must be configured as a “temperature”
Make sure that the value displayed, is the real and accurate temperature value.
When configuring Ex20 Modbus in the RTU gateway, make sure to select "galooli_ex20modbus_IN12T". Due to this configuration, input 12 will be defined as "temperature" and accurate data will be obtained
In the RTU gateway status, the value is displayed in resistance units. For example when the temperature is 25 degrees Celsius, the value is 10000, and as the temperature rises, the value decreases. By knowing that, you can ensure that the value is reasonable.
In the Panorama application, according to the layout, the resistance value is converted to the temperature value.