A/C Current Sensor
AC ring sensors are used to detect loads going to the air conditioner and provide the status of the air conditioner.
On/Off AC Current sensor (Air Condition)
Self-powered, AC current sensing device, providing on/off status of electric loads including fans, pumps, motors, heaters, and virtually any AC powered device.
Features:
Low turn-on (less than 0.150 A)
Hysteresis and anti-transient circuitry
eliminates chatter and false switchingEasy Wiring
Rugged enclosure
Technical Specification | |
Power | Self Powered from the monitored line. |
Current Input | 0.150 to 100A |
 Output | Bi-directional, normally open relay. |
Switch Point | ≤ 150mA |
Hysteresis | ~10mA (ie: on at 150mA, off at 140mA) |
Enclosure | ABS (UL 94V-0) Plastic box 2"x1.6"x0.9" |
Weight | 2.4 oz (68 g) |
Wire Window | 0.54" (13.7 mm) |
Terminal Block (-S) | Barrier Strip. Accepts up to 12-26AWG |
Lead Length (-S-w) | 6" (15 cm) |
  Standards and Certifications |
|
 Additional Information
Part Number:
Manufacturer's website - Elkor Technologies Inc. - Welcome
Manufacturer PN. - i-Snail-S
Galooli PN. - 400-ACCurStaD-036
Manufacturer datasheet