CE Transducer CE42

The AC Meter is a three-phase electrical isolation transducer.

Features:

  • Three-phase energy analyzer

  • RS485 communication port

  • Easy installation

Technical Specification

Rated voltage:

0-1000V

Rated current (direct):

0-200A

Operating temperature

-10~+55°C

Power supply

12V (9.6V~16V)

Baud rate:

19200, 9600(default), 4800, 2400, 1200

Isolation voltage

2500 V DC

A/D speed

≤100mS

Meter voltage reading accuracy

±0.5%

Meter current reading accuracy

±0.5%

Technical Specifications

  • manufacturer's website - SSET

  • Manufacturer PN. - CE--AJ42B-32DS5-0.5,1000V*200A

  • Galooli PN. - 400-ACMetAJ42B-502

  • Manufacturer datasheet

Pinout Diagram

 

Pin #

Name

Pin #

Name

1

PHASE 1 Voltage (input)

2

PHASE 2 Voltage (input)

3

PHASE 3 Voltage (input)

4

N

16

RS3485 A

15

RS3485 B

14

VSS

7

12V+ (Power in)

8

V-(GND)