Skip to end of banner
Go to start of banner

Section: Global DC

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 11 Current »

The purpose of this section is to describe the global DC alarms.

If the alarm was active it will keep active as

Item

The Affected Digital Alarm/Dashboards

Default Values

Voltage Threshold LVD

 Site_Global.DC_Alarm_LVD

 

43.5 V

Voltage Threshold LVD Release

 49V

Voltage Threshold BLV

 Site_Global.DC_Alarm_BLV

 48V

Voltage Threshold BLV Release

 50V

Voltage Threshold PLD

 Site_Global.DC_Alarm_PLD

 

 45.5V

Voltage Threshold PLD Release

51V

Voltage Threshold Generator Fail To Start

Site_Global.Generator_X_Fail_To_Start

*Hard coded release - 49.3V

48.3V

  • No labels