The purpose of this section is to describe the global DC alarms.
If *In the event that the alarm was becomes active, it will keep active asremain active until the release threshold value is reached
Item | The Affected Digital Alarm/Dashboards | Default Values |
---|---|---|
Voltage Threshold LVD | Site_Global.DC_Alarm_LVD
| 43.5 V |
Voltage Threshold LVD Release | 49V | |
Voltage Threshold BLV | Site_Global.DC_Alarm_BLV | 48V |
Voltage Threshold BLV Release | 50V | |
Voltage Threshold PLD | Site_Global.DC_Alarm_PLD
| 45.5V |
Voltage Threshold PLD Release | 51V | |
Voltage Threshold Generator Fail To Start | Site_Global.Generator_X_Fail_To_Start *Hard coded release - 49.3V | 48.3V |
...