Sparta Installation and Configuration
Preparation
Installation Preparation
Please ensure that you have the following items:
Sparta gateway
Connector for power cables included with Sparta gateway
RS485 connector (Connects the Sparta to the RS485 to USB converter)
Cable lug. Specifications: insulated ring-type lug. Inner Dia: 6.4mm, stud size: M6, Cable size 0.5-2.5mm
Thick double side adhesive. Specifications: Thickness-2mm, width-30cm, material - Nano PU gel
If you wish to conceal Sparta inside of the battery box so that it will not be visible, then you will need to bring a special glue/silicone for this purpose
Torque wrench
Plier
Screwdriver
Adjustable spanner
RS485 To USB Converter & two 0.5mm thick communication cables. The length of the cables is determined by the distance between the RS485 to the USB converter and the computer
Configuration Preparation
A computer with an internet connection is required
Power Center installed - Click here to download. Credential info can be received from your Account Manager or Galooli support
Login credentials for Galooli Solution
RS485 to USB converter - Refer here for driver installation instructions.
Battery Connection & Power
Sparta gateway may be mounted either on the battery box or inside it. To be hidden, Sparta must be inserted inside the battery box.
Place the Sparta gateway in the desired location on the battery according to your requirements (outside or inside the battery box).
Connect the Sparta gateway to the battery, connect the red wires to the plus side and the black wires to the minus side.
Outside-the-box connection
Inside-the-box connection
It is now necessary to connect the Sparta gateway to the computer for configuration.
Power Center Configuration
Connect the RS485 connector to the Sparta input.
Pin # | Name | |
---|---|---|
1 | RS485-A (Red) | |
2 | RS485-B (Black) | |
3 | GND (Yellow) - Inactive |
Connect the other side of the RS485 connector to the RS485 to USB converter.
Pin # | Color | RS485 Converter | |
---|---|---|---|
1 - RS485 A | Red | Input 1 | |
2 - RS485 B | Black | Input 2 |
Connect the RS485 converter to the computer
Open the Power Center
Open the “Active Device” drop-down menu, and select “Power Device”.
Open the “Connect Via” drop-down menu, and select the relevant Serial COM port.
Chose the “Sparta” tab
By double-clicking on the "Messages" option, a new tab will be opened with the name "Communication Log". You should drag this tab to the right side of the Power Center until you see a square icon. Locate the computer's mouse in this square and drop the "Communication Log" there. This action will locate the "Communication Log" in a convenient location so that it can be viewed to determine whether there has been communication with Sparta.
After that, click the “Sparta” tab again.
Ensure that the "Communication log" is filled with data.
Click on “Read Configuration” and then “Status”.
If it is necessary to change Sparta’s default parameters, please refer to the following section.
This section describes the changes that are made to Sparta when the user is physically connected to it. In the event that the connection is not physical, but rather via wireless connection (OTA), the Sparta should be set to "Maintenance Mode" in order to make any configuration changes.
Sparta Lead-acid Battery | Modes
Server URL
The address of the Galooli Server for the purpose of transferring data. This information can be found in the technical booklet of the organization.Network APN
The following is a list of all the global SIM cards that Galooli offers. There will be a different APN for each local carrier.
SIM card address:
Telefónica Digital Solutions - M2M & IoT (telefonica)
internet.gma.iot (t-mobile)
bicsapn (BICS)
Network User
There are some cellular operators that require a username for each SIM card. In the absence of a mention, move on.Network Password
There are some cellular operators that require a password for each SIM card. In the absence of a mention, move on.Out of storage voltage [V]
When a certain voltage is applied, the Sparta will move from the “Storage” mode to the “In Cabinet” mode. 13.1V as a default.Storage Sampling Interval [Minutes]
The interval during "Storage" mode when the Sparta will check its own status. During the test, no information is recorded or sent to the server, but only an internal test is conducted. The Sparta uses this method to determine whether it should move to another status set by the user. The default is every 60 minutes.In-Cabinet Metrics Interval [Minutes]
The duration of Sparta connection to the server during each interval. 5 minutes is the default time.In-Cabinet Wakeup Interval [Hours]
Sparta frequency of connection to the server. 24 hours is the default time.
Note: A serial connection can be made at any time. OTA connection can be made only in this period of time.GPS state while in-Cabinet
The GPS receiver status is controlled while the Sparta is in the "In Cabinet" mode. The Sparta location will not be sent to the server during the "In Cabinet" wakeup interval if the box is unchecked.Report Intervals [seconds]
Sets how often the Sparta transmits information to the server once the unit is in “Tracking” mode.60 seconds is the default time.
Movement Sensor Sensitivity
Defines the Sensitivity level of the accelerometer (motion sensor).
Normal is the default.Disable User Interface
In the event that this option is checked, the Sparta's LEDs will not be illuminated.Enable Silk Route™ Technology
With this option enabled, Sparta's track trail display on the map will be more accurate and uninterrupted while in "tracking" mode. Consequently, more power and data are consumed.
Ensure that the Sparta hardware version is up-to-date, if necessary update the version. After an upgrade has occurred, click on “Write configuration”.
Whenever a serial connection is used, the version upgrade must be performed in "Maintenance" mode.
In order to upgrade the Sparta version wirelessly (OTA), you must wait for the Sparta "In Cabinet" interval, connect, switch to maintenance mode, and then upgrade the Sparta version.
Version updates can be performed through the Power Center or through the Galooli Solution.
My Versions
Galooli Solution Configuration
Organization Tree
Open the Galooli Solution >> Click on the “Manager” application >> Click on “My Units” >> It is recommended that you create meaningful clusters and groups in your organization tree that will assist you in managing all future units. My Units
Unit Configuration
In the event that you own an active Sparta gateway in your organization, you can copy all or part of the configurations to the new Sparta gateway using the "Copy Settings” tool or “Clone Unit” option.
In the event, this is the organization's first Sparta gateway, please continue to the first paragraph.
Find the relevant unit within the "Stock" cluster and click on it. My Unit
The "Overview" tab should be used to give the unit a name, a description, and an asset type. Set the "Stationary Unit" to "No". Set the destination Email and SMS. Email and phone numbers can be set at the cluster or group level as opposed to the unit level. The remainder of the information can be filled in as needed. https://galooli.atlassian.net/l/cp/GUAkk1K4
On the "Events" tab, add the relevant events. https://galooli.atlassian.net/l/cp/zjX0vNmg
Click on “Save”
Transfer the unit from the "Stock" cluster to another relevant cluster. https://galooli.atlassian.net/l/cp/J6c4DHE1
Verify that the unit can be seen on the Panorama map and that the Panorama time stamp is being updated. https://galooli.atlassian.net/l/cp/hth1o23t
Please follow the next link if the location of the unit is incorrect or not set at all - Sparta Lead-acid Battery | Manual Location Setup