Battery Cell Monitoring - Elara Configuration

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 10 Current »

In the event that a preliminary configuration process between Elara and the rectifier has already been completed, proceed to the “Adding Modbus ETH Device” section listed below.

If the configuration process between Elara and the rectifier is not necessary, change the IP address manually before proceeding to the “Adding Modbus ETH Device”.

  1. Double-click the “Network” row

2. Change the data settings to the following values:
Network Mask - 255.255.255.0
Network Gateway - 192.168.100.1
Elara IP - 192.168.100.101

3. Click on “Write Configuration”

Adding Modbus ETH Devices

  1. Click on the “Configuration” tab

  2. Add a Modbus ETH device

  3. The relevant devices should be selected as described in the image below. All of the steps described from this step and below should be performed on the second string if you are working with two strings.

  4. If you have configured the rectifier, take note of the hub IP address that you have configured in the "Hub Configuration" section. If no configuration is required for the rectifier, write the default hub IP address 192.168.8.100.

  5. Apply the changes

6. Click on “Write Configuration”

7. In the case of two strings, go back to step 3 and select the second string. Then, repeat the process for the second string.