Monitoring system for Lead Acid batteries health. Features numerous advantages, making it suitable for a wide range of applications.


Features:

  • Monitor Battery String Voltage, Charge, and Discharge Current, String balance, Resistance, and Temperature

  • Supports 2 Strings, Max. 60pcs batteries for each string

  • Calculate Battery String SOC and SOH

  • Auto-Balancing

  • Auto-sensing for the Battery Sensor's ID Address

Technical Specification

Battery Cell Monitoring HUB

Rated Input Voltage

24V DC

Voltage

0V ~ 800V ( Accuracy: ±0.5% )

Current

-1000A ~ +1000AV ( by Hall Sensor, Accuracy: ±2.0%)

Power Comsumption

< 2W

Technical Specification

Battery Cell Monitoring Sensor

Rated Input Voltage

2V

12V

Voltage

1.6V~2.6V (±0.2%)

7.5V~15.6V (±0.2%)

Internal Temperature

-20°C~85°C (±0.5%)

Impedance

0.1mΩ~100mΩ

conformity error: 1.5%±25uΩ

Power Consumption

Running: <110mW Sleeping: <12mW

Running: <90mW Sleeping: <10mW

Technical Specification

Battery Cell Monitoring Hall Sensor

Rated primary input current

100A

Primary current measure range

0~±200A

Power supply

+5(±5%)V

Current consumption

25mA

Ambient temperature

-25~+85℃

Storage temperature

-40~+100℃

Load resistance

≥10K