Field Name | Field Description | Calculation Method |
---|---|---|
Tenant X Initial [KWH] | The first record of the kWh value was read from the tenant's meter, for the selected time range. |
|
Tenant X Final [KWH] | The last record of the kWh value was read from the tenant's meter, for the selected time range. | |
Tenant X Total [KWH] | The total energy consumption (kWh) of the tenant, is based on the readings from the tenant's meter. | |
Tenant X Total DG [KWH] | The total energy consumption (kWh) of the tenant that was received from the generator, is based on the readings from the tenant's meter. | Based on the field Colo_Meter_X.Total_DG_KWH [KWH] |
| The total energy consumption (kWh) of the tenant that was not received from the generator, is based on the readings from the tenant's meter. | Based on the fields Colo_Meter_X.Total_KWH [KWH],
|
Tenant X Assignment | The assignment (name) of tenant X. | |
Tenant X Min/Max/Avg Current [A] | The minimum, maximum and average current of the tenant's meter. | |
Tenant X Min/Max/Avg Voltage [V] | The minimum, maximum, and average voltage of the tenant's meter. | |
| The total time in the day (hours) the tenant's "Power Down" alarm was false, meaning the tenant received voltage. | Based on records where Colo_Meter_X_Alarm_Power_Down = No. |
| The total time in the day (hours) the tenant's "Load Down" alarm was false, meaning the tenant received current. | |
| The calculated energy consumption (kWh) of the tenant, is based on voltage and the current provided to the tenant. | Based on the fields Colo_Meter_X.V_LY [V], Colo_Meter_X.I_LY [V] X=1->20, Y=1->3 |
The availability time is calculated by accumulating the time between records where the relevant asset was connected. The time will be reserved only if the time difference between the subsequent records is less than 15* minutes. In addition, if the calculated availability value is larger than the Data Availability value, the value will be assigned with the Data Availability value.