Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The purpose of this section is to describe the XX XX XX.global DC alarms.

*In the event that the alarm becomes active, it will remain active until the release threshold value is reached

Item

The Affected Digital Alarm/Dashboards

Default Values

Voltage Threshold LVD

 Site_Global.DC_Alarm_LVD

 

43.5 V

Voltage Threshold LVD Release

 

 49 49V

Voltage Threshold BLV

 

 Site_Global.DC_Alarm_BLV

 48V

Voltage Threshold BLV Release

 

 50V

Voltage Threshold PLD

 Site_Global.DC_Alarm_PLD

 

 45.55V

Voltage Threshold PLD Release

5151V

Voltage Threshold Generator Fail To Start

Site_Global.Generator_X_Fail_To_Start

*Hard coded release - 49.3V

48.33V