The purpose of this section is to describe the XX XX XX.global DC alarms.
*In the event that the alarm becomes active, it will remain active until the release threshold value is reached
Item | The Affected Digital Alarm/Dashboards | Default Values | |
---|---|---|---|
Voltage Threshold LVD | Site_Global.DC_Alarm_LVD
| 43.5 V | |
Voltage Threshold LVD Release | 49V |
| |
Voltage Threshold BLV |
| Site_Global.DC_Alarm_BLV | 48V |
Voltage Threshold BLV Release | 50V |
| |
Voltage Threshold PLD | Site_Global.DC_Alarm_PLD
| 45.5V | |
Voltage Threshold PLD Release | 51V | ||
Voltage Threshold Generator Fail To Start | Site_Global.Generator_X_Fail_To_Start *Hard coded release - 49.3V | 48.3V |