Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Item

The Affected Digital Alarms/Dashboards

Thresholds

Field Meaning and Logic



High Voltage Threshold




Site_Global.Grid_High_Voltage

*Active if at least one configured phase is above the threshold

 


260

If this threshold is exceeded, the grid might cause damage to electronic and electrical equipment. An alert will be generated if the value exceeds the threshold

By using the new thresholds, you can determine the values that will impact the alerts of grid availability and high voltage so they can be adapted to both 220 and 110-volt networks.





Minimal Voltage Threshold

Site_Global.Grid_Availiable
*Active if at least one configured phase is above the threshold

Site_Global.Grid_Partly_Availiable

*Active if at least one configured phase is above the threshold and one configured phase is below the threshold

Site_Global.Grid_Fail

*Active if all the configured phases are below the threshold

 

90 

The minimal voltage level of the grid, so the grid will be defined as “available”. If the value falls below the threshold, an alert will be generated

By using the new thresholds, you can determine the values that will impact the alerts of grid availability and high voltage so they can be adapted to both 220 and 110-volt networks.

Cost Per KWh

Site Costs Dashboard

 0.16