NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. You can get a good idea of the extreme conditions on site based on the alarms. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.
Table of Contents |
---|
Environment Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name - NEW
...
1
...
A/C Fault
...
At least 1 of the Shelter A/C alarm is active
...
Shelter_X.Alarm Galooli AirCondition Y
...
2
...
AWL Fault
...
Aviation/Aircraft Warning Light is OFF
...
Site_Global.Alarm Galooli Aviation Light Fail
...
3
...
Fence Alarm
...
Fence intrusion detection alarm is active
...
Site_Global.Alarm Galooli Fence
...
4
...
Gate Alarm
...
The alarm is active if at least one of the alarms (Entrance/Fence) is true.
...
Site_Global.Alarm Galooli Entrance
...
5
...
High Temp General
...
At least 1 shelter temperature is above the set high-temperature threshold
...
Shelter_X.Alarm Galooli Temperature
...
6
...
High Temp Shelter X
...
Temperature is above the set high-temperature threshold
...
Shelter_X.Alarm Galooli Temperature Very High
...
7
...
Intrusion Alarm
...
At least 1 of the Shelter Door is Open
...
Shelter_X.Alarm Internal Door Open
...
8
...
Smoke Alarm
...
At least 1 of the Shelter Smoke alarms is active in 1 or more of the 5 shelters
...
Shelter_X.Alarm Internal Smoke
...
9
...
Very High Temp General
...
At least one shelter temperature is above the set Very-high-temperature threshold
...
Shelter_X.Alarm Galooli Temperature
...
10
...
Very High Temp Shelter X
...
Temperature is above the set Very high-temperature threshold.
...
Shelter_X.Alarm Galooli Temperature Very High
Fuel Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name & Logic
...
1
...
Fuel Drop
...
Fuel drop of 10 liters and above. The alarm is deactivated after 1 hour.
The data is recorded and displayed in the Galooli solution until the next drop.
...
Generator.Fuel Alerts.Last Drop
...
2
...
High Level
...
If Site Global Fuel 1-2/Tank Max Capacity > 0.9. The ‘Tank Max Capacity’ is determined according to the fuel’s calibration table
...
Site Global Fuel X/Tank Max Capacity
...
3
...
Level Low
...
1 of the fuel level is low
...
Site_Global.Alarm_Fuel_X_Low
...
4
...
Level Very Low
...
1 of the fuel level is very low
...
Site_Global.Alarm_Fuel_X_VeryLow
Generator Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name
...
NEW
...
1
...
Generator Fault
...
At least 1 Generator alarm is on
...
(Generator_X.Alarm Galooli Active) && !(Site_Global.Alarm Galooli Generator X Fail To Start)
...
2
...
Battery High
...
At least one of Generator_X.Battery_High is true
...
Generator_X.Alarm Galooli Battery High
...
3
...
Battery Low
...
At least one of the generators battery voltage is low
...
Generator_X.Battery_low
...
Generator_X.Alarm Galooli Battery Low
...
4
...
Charge Alternator Fail
...
At least one of Generator_X.Charge_Alternator_Fail is true
...
Generator_X.Alarm Internal Alternator fail
...
5
...
Generator Controller Fault
...
No communication between the Gen controller and Galooli RTU, controller data is not available.
...
Generator_X.Disconnected
...
Generator_X.Disconnected
...
6
...
Door Open
...
At least one of Generator_X.Door_Open is true
...
Generator_X.Alarm Internal Door Open
...
7
...
Emergency Stop
...
Generator Emergency Stop occurred
...
Generator_X.Emergency_stop
...
Generator_X.Alarm Internal Emergency Stop
8
Engine Hours Tampering
...
The alarm become active when the difference in engine hours eXceeds the difference in records by more than two hours.
It is essential that the NOC alarm is configured with an “Activation Delay time: 0” and a long “Release Delay time” in order to detect the alarm effectively (the above flag will only be True for one transmission of the unit and will be canceled by the time of the neXt transmission).
...
Generator_X.Engine_Hours_Tampering
...
Generator_X.Alarm Galooli Engine Hours Tampering
9
Generator Fail To Start
...
For hybrid sites: the alarm will be active when DC voltage (Site Global.U_System) ≤ Generator fail to start threshold and Gen is “off” and another power source not available.
For non-hybrid sites: the alarm will be active if “Site_Global.AC_Fail” is “True”, or “Generator_1.Fail_To_Start” is “True” (reading from the generator panel)
...
Site_Global.GeneratorX_Fail_To_Start
NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. You can get a good idea of the extreme conditions on site based on the alarms. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.
Panel | ||||||
---|---|---|---|---|---|---|
| ||||||
System Thresholds - NOC alarms are affected by Galooli "System Thresholds", which can be changed by the user through the Galooli Solution. The NOC alarm types listed below include system thresholds data. https://galooli.atlassian.net/wiki/spaces/KP/pages/2802450433/My+Units#KPIs-Breakdown |
Table of Contents |
---|
Discrete Inputs
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds |
1 | Digital 1-20 | Alarms related to digital inputs in the system will be triggered only if the digital I/O returns a "True" status. Note: Alarms will not be triggered if the relevant digital input (1-20) is not configured in My Units → Edit Unit → Configuration → I/O's → Input → Digital. |
|
Environment Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds |
1 | A/C Fault | At least 1 of the Shelter A/C alarm is active | Shelter_X.Alarm Galooli AirCondition Y | |
2 | AWL Fault | Aviation/Aircraft Warning Light is OFF | Site_Global.Alarm Galooli Aviation Light Fail | |
3 | Fence Alarm | Fence intrusion detection alarm is active | Site_Global.Alarm Galooli Fence | |
4 | Gate Alarm | The alarm is active if at least one of the alarms (Entrance/Fence) is true. | Site_Global.Alarm Galooli Entrance | |
5 | High Temp General | At least 1 shelter temperature is above the set high-temperature threshold | Shelter_X.Alarm Galooli Temperature |
|
6 | High Temp Shelter X | Temperature is above the set high-temperature threshold | Shelter_X.Alarm Galooli Temperature Very High | |
7 | Intrusion Alarm | At least 1 of the Shelter Door is Open | Shelter_X.Alarm Internal Door Open | |
8 | Motion Alarm | Triggered when Shelter_X.Alarm_Internal_Motion (at least one) is “True”. | Shelter_X.Alarm_Internal_Motion | |
9 | Smoke Alarm | At least 1 of the Shelter Smoke alarms is active in 1 or more of the 5 shelters | Shelter_X.Alarm Internal Smoke | |
10 | Very High Temp General | At least one shelter temperature is above the set Very-high-temperature threshold | Shelter_X.Alarm Galooli Temperature |
|
11 | Very High Temp Shelter X | Temperature is above the set Very high-temperature threshold. | Shelter_X.Alarm Galooli Temperature Very High | |
12 | Vibration Alarm | Triggered when Shelter_X.Alarm_Internal_Vibration (at least one) is “True”. | Shelter_X.Alarm_Internal_Vibration |
Fuel Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | |
1 | Fuel Drop | Fuel drop of 10 liters and above. The organization has the flexibility to configure the Release Delay Time of the alarm. The data is recorded and displayed in the Galooli solution until the next drop. | Generator.Fuel Alerts.Last Drop | |
2 | High Level | If Site Global Fuel 1-2/Tank Max Capacity > 0.9. The ‘Tank Max Capacity’ is determined according to the fuel’s calibration table | Site Global Fuel X/Tank Max Capacity | |
3 | Level Low | 1 of the fuel level is low | Site_Global.Alarm_Fuel_X_Low |
|
4 | Level Very Low | 1 of the fuel level is very low | Site_Global.Alarm_Fuel_X_VeryLow |
|
Generator Alarms
...
4
...
Extension Disconnected
...
One of the eXtensions is disconnected
...
Site_Global.EX20ETH_X_Disconnected || Site_Global.EX20_X_Disconnected
...
Site_Global.EX20ETH_X_Disconnected || Site_Global.EX20_X_Disconnected
...
5
...
Fuel Sensor Disconnected
...
No communication between the Fuel sensor and the Galooli RTU
...
Site_Global.Fuel_X_Disconnected
...
Site_Global.Fuel_X_Disconnected
...
6
...
Output Active
...
TBA
...
Site_Global.Output_Active
...
Site_Global.Output_Active
...
7
...
Temperature Sensor Fault
...
The temperature sensor in at least 1 of the shelter is out of range, mostly not real
...
(Shelter_X.Room_Temperature > 55) || (Shelter_X.Room_Temperature < 0)
...
(Shelter_X.Room_Temperature > 55) || (Shelter_X.Room_Temperature < 0)
...
8
...
Tenant 1 - 20
Meter Disconnected
...
At least 1 of the 20 Tenant meters is currently Disconnected
...
Colo_Meter_X.Disconnected
...
Tenant_X.Disconnected
...
9
...
Unit Disconnected
...
No communication between Galooli RTU and the server
...
Status = Disconnected
...
Status = Disconnected
Inverter Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name
...
NEW
...
1
...
Solar Alarm
...
If any of the inverter's solar alarms are true, the alarm is on
...
Inverter_X.Solar_Y_Alarm_Active
...
Inverter_X.Alarm Internal Solar Y
Power Alarms
Alarm Number
Alarm Name
Description
System Parameter Name
NEW
1
AC Meter Grid Low PF
0 < ABS(AC_Meter_Grid.PF_LX) < 0.8 (The absolute value of the power factor is greater than 0 and less than 0.8)
AND
ABS(AC_Meter_Grid.I_LX) > 1[A] (The absolute value of the current is greater than 1)
2
Battery High Current
The alarm is true if the digital 'Site Global Alarm High Battery Current' is true.
Site Global Alarm High Battery Current
Site_Global.Alarm Galooli High Battery Current
3
BLV Alarm
This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold - Section: Global DC
Site_Global.DC_Alarm_BLV
Site_Global.Alarm Galooli DC BLV
4
Consumers' Load Drop
If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active.
As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report).
If (Unit KPI Field)‘Current Threshold Site Down'> 0, check if 'Site Global Consumers Load Power' < (Site Global U System’ * threshold
Site_Global.Alarm_Consumers_Load_Drop.
Site_Global.Alarm Galooli Consumers Load Drop
5
Consumers Load High
The alarm is true if 'Site Global Consumers Load Power' > threshold, and threshold > 0.
Threshold - unit KPI → Consumers → ‘High Consumers Power Threshold
Site Global Consumers Load Power
Site_Global.Consumers_Load_Power [W]
6
Generator Running > 3 Hours
Generator_X.Is_Running
7
Generator running and battery discharging
The Generator running but battery is discharging
Site_Global.Alarm_Generator_Running_Bat_Discharge
Site_Global.Alarm Galooli Generator Running Battery Discharge
8
Generator Running and Battery not Charging
If site is hybrid AND ‘Site Global.Generator_1-2_Running’ AND ‘Site Global.Battery Charging’ is false
Site Global.Generator_X_Running
and
Site Global.Battery Charging
Site Global.Generator_X_Running
and
Site Global.Battery Charging
9
Grid High Current
Threshold - unit KPI → Grid → 'High Current Threshold
?
10
Grid High Voltage
Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid eXceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active.
Section: Grid*
Gird_High_Voltage
?
11
Grid Partly Available
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds | ||
1 | Generator Fault | At least 1 Generator alarm is on | (Generator_X.Alarm Galooli Active) && !(Site_Global.Alarm Galooli Generator X Fail To Start) | |||
10 | Generator Fail To Stop | Grid available and Generator is running or Generator_1.Fail_To_Stop is true (reading from the generator panel) | Generator_X_Fail_To_Stop2 | Battery High | At least one of Generator_X.Battery_High is true | Generator_X.Alarm | Internal Fail to stop
11 | High Coolant | Generator High Coolant indication | Generator_X.High_coolant | Generator_X.Alarm Internal High Coolant | ||
12 | Low Coolant | At least one of Generator_X.Low Coolant is true | Generator_X.Indication Internal Low Coolant | 13 | High Load PowerGalooli Battery High |
|
3 | Battery Low | At least one of the generators battery voltage is low | Generator_X.Alarm Galooli Battery Low |
| ||
4 | Charge Alternator Fail | At least one of 'SiteGenerator_GlobalX.GeneratorCharge_1-2_High_Load' is true. | Site_Global.Generator_X_High_Load | Site_Global.Alarm Galooli Generator X High Load | ||
14 | Very High Load Power | At least one of 'Site_Global.Generator_1-2_Very_High_Load' is true. | Site_Global.Generator_X_Very_High_Load | Site_Global.Alarm Galooli Generator X Very High Load | ||
15 | High Voltage | Generator High Voltage indication | Generator_X.High_voltage | Generator_X.Alarm Galooli High Voltage | ||
16 | Low Voltage | Generator Low Voltage indication | Generator_X.Low_voltageAlternator_Fail is true | Generator_X.Alarm Internal Alternator fail | ||
5 | Generator Controller Fault | No communication between the Gen controller and Galooli RTU, controller data is not available. | Generator_X.Disconnected | |||
6 | Door Open | At least one of Generator_X.Door_Open is true | Generator_X.Alarm Internal Door Open | |||
7 | Emergency Stop | Generator Emergency Stop occurred | Generator_X.Alarm Internal Emergency Stop | |||
8 | Engine Hours Tampering | The alarm become active when the difference in engine hours eXceeds the difference in records by more than two hours. It is essential that the NOC alarm is configured with an “Activation Delay time: 0” and a long “Release Delay time” in order to detect the alarm effectively (the above flag will only be True for one transmission of the unit and will be canceled by the time of the neXt transmission). | Generator_X.Alarm Galooli | Low VoltageGenerator_X.Alarm Galooli Low Oil Pressure True if Internal Low Oil Pressure is true, AND Generator_X.ls_Running is true | Generator_X.Alarm Galooli Low Oil Pressure | |
18 | Not in Auto | Generator Not in Auto mode | Generator_X.Not_in_AutoMode | Generator_X.Alarm Galooli Not in Auto | ||
19 | Over Frequency | Generator Over Frequency indication | Generator_X.Over_frequency | Generator_X.Alarm Internal Over frequency | ||
20 | Under FrequencyEngine Hours Tampering | |||||
9 | Generator Fail To Start |
| Site_Global.Alarm Galooli Generator X Fail To Start |
| ||
10 | Generator Fail To Stop | Grid available and Generator is running or Generator_1.Fail_To_Stop is true (reading from the generator panel) | Generator_X.Alarm Internal Fail to stop | |||
11 | High Coolant | Generator High Coolant indication | Generator_X.Alarm Internal High Coolant | |||
12 | Low Coolant | At least one of Generator_X.Under_Frequency is Low Coolant is true | Generator_X.Alarm Indication Internal Under frequencyLow Coolant | |||
21 | Running > 10 Hours at Solar Hybrid Site | The site is running on generator more that 10 hours strait and this is a solar hybrid site | Time In Status>10 Hours Site Layout = Solar | Time In Status Site Layout | ||
22 | Running When Grid Available | Gen is running and Grid is available simultaneously for at least 25 minutes | Time In Status>25 Minutes Site_Global.Grid_Avialable | Time In Status Site_Global.Grid Available |
GPS Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name
...
NEW
...
1
...
Tracking
...
Sparta unit, working mode In Tracking alarm
...
Battery_State.Tracking
...
Battery_State.Tracking
Hardware Alarms
...
Alarm Number
...
Alarm Name
...
Description
...
System Parameter Name
...
NEW
...
1
...
AC Meter Grid Disconnected
...
When AC_Meter_Grid.Disconnected = True, this alarm will activated
...
AC_Meter_Grid.Disconnected
...
2
...
ATS Meter Disconnected
...
No communication between ATS Meter and the Galooli RTU
...
AC_Meter_ATS.Disconnected
...
AC_Meter_ATS.Disconnected
...
3
...
Backup Low Voltage
...
Backup Voltage < 3.3V
13 | High Load Power | At least one of 'Site_Global.Generator_1-2_High_Load' is true. | Site_Global.Alarm Galooli Generator X High Load | |
14 | Very High Load Power | At least one of 'Site_Global.Generator_1-2_Very_High_Load' is true. | Site_Global.Alarm Galooli Generator X Very High Load | |
15 | High Voltage | Generator High Voltage indication | Generator_X.Alarm Galooli High Voltage |
|
16 | Low Voltage | Generator Low Voltage indication | Generator_X.Alarm Galooli Low Voltage |
|
17 | Low Oil Pressure | Generator Low Oil Pressure Indication | Generator_X.Alarm Galooli Low Oil Pressure | |
18 | Not in Auto | Generator Not in Auto mode | Generator_X.Alarm Galooli Not in Auto | |
19 | Over Frequency | Generator Over Frequency indication | Generator_X.Alarm Internal Over frequency | |
20 | Under Frequency | At least one of Generator_X.Under_Frequency is true | Generator_X.Alarm Internal Under frequency | |
21 | Running > 10 Hours at Solar Hybrid Site | The site is running on generator more that 10 hours strait and this is a solar hybrid site | Time In Status Site Layout | |
22 | Running When Grid Available | Gen is running and Grid is available simultaneously for at least 25 minutes | Time In Status Site_Global.Grid Available |
GPS Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds |
1 | Tracking | Sparta unit, working mode In Tracking alarm | Battery_State.Tracking |
Hardware Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds |
1 | AC Meter Grid Disconnected | When AC_Meter_Grid.Disconnected = True, this alarm will activated | AC_Meter_Grid.Disconnected | |
2 | ATS Meter Disconnected | No communication between ATS Meter and the Galooli RTU | AC_Meter_ATS.Disconnected | |
3 | Backup Low Voltage | Backup Voltage < 3.3V | ||
4 | Extension Disconnected | One of the eXtensions is disconnected | Site_Global.EX20ETH_X_Disconnected || Site_Global.EX20_X_Disconnected | |
5 | Fuel Sensor Disconnected | No communication between the Fuel sensor and the Galooli RTU | Site_Global.Fuel_X_Disconnected | |
6 | Output Active | TBA | Site_Global.Output_Active | |
7 | Temperature Sensor Fault | The temperature sensor in at least 1 of the shelter is out of range, mostly not real | (Shelter_X.Room_Temperature > 55) || (Shelter_X.Room_Temperature < 0) | |
8 | Tenant 1 - 20 | At least 1 of the 20 Tenant meters is currently Disconnected | Tenant_X.Disconnected | |
9 | Unit Disconnected | No communication between Galooli RTU and the server | Status = Disconnected |
Location Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds |
1 | Geofence Enter | The alarm is active when the unit enters the geofence | For the alarm to function properly, it is essential to first create “Location Event” in the system, as outlined in the following document - https://galooli.atlassian.net/l/cp/0A4wjbTt | |
2 | Geofence Leave | The alarm is active when the unit leaves the geofence |
Power Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | System Thresholds | ||||||||
1 | AC Meter Grid Low PF | In order to ensure that there are no false alarms regarding the AC meter grid low power factor at least in one phase, the system checks that the PF is greater than 0 and the current of the phase is higher than 1. |
AND
| |||||||||
2 | Battery High Current | The alarm is true if the digital 'Site Global Alarm High Battery Current' is true. | Site_Global.Alarm Galooli High Battery Current |
| ||||||||
|
| This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold - Section: Global DC |
|
| ||||||||
4 | Consumers' Load Drop | If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active. As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report). If (Unit KPI Field)‘Consumers Load Drop Current Threshold'> 0, check if 'Site Global Consumers Load Power' < (Site Global U System’ * threshold | Site_Global.Alarm Galooli Consumers Load Drop |
| ||||||||
5 | Consumers Load High | The alarm is true if 'Site Global Consumers Load Power' > threshold, and threshold > 0. Threshold - unit KPI → Consumers → ‘High Consumers Power Threshold | Site_Global.Consumers_Load_Power [W] |
| ||||||||
6 | Generator Running > 3 Hours | The alarm is intended to ensure that there is a logical reason for the generator to run longer than three hours. In order to obtain information about more than three hours, you must change the Activation Delay time - https://galooli.atlassian.net/wiki | /x/CwDYtSite_Global.Grid_Partly_Availabale | Site_Global.Alarm Galooli Grid Partly Available | 12 | High System DC Voltage/spaces/KP/pages/2483945485/Galooli+NOC+Application#Add-Alarm | Time is status > 3 hours | |||||
7 | Generator running and battery discharging | The Generator running but battery is discharging | Site_Global.Alarm Galooli Generator Running Battery Discharge | |||||||||
8 | Generator Running and Battery not Charging | If site is hybrid AND ‘Site Global.Generator_1-2_Running’ AND ‘Site Global.Battery Charging’ is false | Site Global.Generator_X_Running | |||||||||
9 | Grid High Current | Thealarm is true if | the digital 'Site Global Alarm High System Voltage’ is true.Site Global Alarm High System Voltage | Site_Global.Alarm Galooli High System Voltage | 13 |
LVD Alarm | This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. Section: Global DC At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage. |
Site_Global.DC_Alarm_LVD |
14 | for at least one phase ABS(Site Global Grid_I1-3) > threshold, and threshold > 0. Threshold - unit KPI → Grid → 'High Current Threshold | Site Global Grid_I1-3 > threshold, and threshold > 0. | |
10 | Grid High Voltage | Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid exceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active. | Side Global Alarm Galooli Gird_High_Voltage |
| ||||||||
11 | Grid Partly Available | Grid only partly available indication - https://galooli.atlassian.net/wiki/x/CwDYt | Site_Global.Grid_Fail && Site_Global.Is_Planned_Grid_FailAlarm Galooli Grid Partly Available | |||||||||
12 | High System DC Voltage | The alarm is true if the digital 'Site Global Alarm High System Voltage’ is true. | Site_Global.Grid_Fail && Site_Global.Is_Planned_Grid_Fail 15 No AC Load No AC power to the Rectifier Site_Global.AC_Fail || ( Non Hybrid && (AC_Meter_ATS.Configured) && !(AC_Meter_ATS.Disconnected && (AC_Meter_ATS.I_LX=0) || (AC_Meter_Grid.Configured) && !(AC_Meter_Grid.Disconnected && (AC_Meter_Grid.I_LX=0) )Alarm Galooli High System Voltage |
| ||||||||
13 |
LVD Alarm | This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. Section: Global DC At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage. | Site_Global.Alarm Galooli DC LVD |
| ||||||||
14 | No Mains | Grid is currently not available If Grid Fail is True and Site_Global.Is_Planned_Grid_Fail is False | Site_Global.Grid_Fail && Site_Global.Is_Planned_Grid_Fail | |||||||||
15 | No AC Load | No AC power to the Rectifier | Site_Global.AC_Fail || ( Non Hybrid && (AC_Meter_ATS.Configured) && !(AC_Meter_ATS.Disconnected && (AC_Meter_ATS.I_LX=0) || (AC_Meter_Grid.Configured) && !(AC_Meter_Grid.Disconnected && (AC_Meter_Grid.I_LX=0) ) | |||||||||
16 | Other on Load | Galooli RTU can not determine the Site power sourceSite_Global.Unknown_On_Load | Site_Global.Other On Load | |||||||||
17 |
PLD Alarm | This is a DC voltage threshold - the system will trigger a Partial Load Disconnect) alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. At this voltage, the rectifier begins disconnecting none essential Loads to save battery energy for essential loads. | Site_Global.DC_Alarm_PLDSite_Global.Alarm Galooli DC PLDAlarm Galooli DC PLD |
| ||||||||
18 | Power Supply Failure | No power to Galooli RTU | EXternal External Voltage < 9V | ?|||||||||
19 | Site on Batteries | The site is currently powered by BatterySite_Global.Alarm_ Battery_On_Load | Site_Global.Alarm Galooli Battery On Load | |||||||||
20 | Smart Batteries Alarm Active | At least 1 smart battery alarm is activeSmart_Battery_X.Alarms are not blank, 0 or indicator | Smart_Battery_X.Alarms are not blank, 0 or indicator | |||||||||
21 | Smart Batteries Disconnected | At least 1 of the Smart Batteries is currently not communicating with the Galooli RTU Smart_Battery_X.Disconnected | Smart_Battery_X.Disconnected | |||||||||
22 | Tenant load drop | If | ColoTenant_ | Meter_X.I_L1+2+3 < 50% of | Colo Tenant X Average Current then the alarm active | Tenant | _X | .Alarm | _Galooli Load | _Drop Drop | ? |
Rectifier Alarms
Alarm Number | Alarm Name | Description | System Parameter Name | NEWSystem Thresholds | |||||
1 | Non-Urgent | At least 1 critical mapped alarm is triggered on the rectifier Rectifier_X_Alarm_Non_Urgent triggered on the rectifier | Rectifier_X.Alarms Non Urgent | ||||||
2 | AC Surge Protector Fault | At least one of Rectifier_X.Alarm_AC_SPD_Fault is trueRectifier_X.Alarm_AC_SPD_Fault | Rectifier_X.Alarm Internal AC SPD Fail | ||||||
3 | Alarms Suppressed | It is an alarm from the rectifier that indicates that other alarms have been configured not to be active, leading to alerts not being received by the user.Rectifier_X.Alarm_Alarms_Suppressed | Rectifier_X.Alarm Internal Suppressed Alarms | ||||||
4 | Battery Alarm | Rectifier's internal battery alarmRectifier_X.Alarm_Internal_battery | Rectifier_X.Alarm Internal Battery | ||||||
5 | Battery Door Open | At least one of 'Rectifier_X.Alarm_Battery_Door' is trueRectifier_X.Alarm_Battery_Door | Rectifier_X.Alarm Internal Battery Door Open | ||||||
6 | BLV | Rectifier's internal battery low voltage alarmRectifier_X.Alarm_Internal_BLV | Rectifier_X.Alarm Internal BLV | ||||||
7 | Critical Alarm | At least 1 critical mapped alarm is triggered on the rectifier but not internal main failure(Rectifier_X.Alarm_Critical) && ! (Rectifier_X.Alarm_Internal_Mains_failure)main failure | (Rectifier_X.Alarm_Critical) && ! (Rectifier_X.Alarm_Internal_Mains_failure) | ||||||
8 | DC Surge Protector Fault | At least one of Rectifier_X.Alarm_DC_SPD_Fault is trueRectifier_X.Alarm_DC_SPD_Fault | Rectifier_X.Alarm Internal DC SPD Fail | ||||||
9 | Disconnected | No communication between the rectifier panel and the Galooli RTU | Rectifier_X.Disconnected | Rectifier_X.Disconnected | |||||
10 | High Battery Temp | Rectifier's internal High Battery Temp alarm Rectifier_X.Temperature_Battery > 37 | Rectifier_X.Alarm Internal Battery Temperature | ||||||
11 | HW Failure | Rectifier's internal HW Failure alarmRectifier_X. alarm_Internal_HW_failure | Rectifier_X.alarm_Internal_HW_failure | ||||||
12 | Load Breaker | Rectifier's internal Load Breaker alarmRectifier_X.Alarm_Internal_Load_Breaker | Rectifier_X.Alarm_Internal_Load_Breaker | ||||||
13 | LVD | Rectifier's internal Low Voltage Disconnect alarm | Rectifier_X.Alarm_Internal_LVD | Rectifier_X.Alarm_Internal_LVD | |||||
14 | Mains Failure | Rectifier's internal Mains Failure alarmRectifier_X.Alarm_Internal_Mains_failure | Rectifier_X.Alarm_Internal_Mains_failure | ||||||
15 | MCB | Rectifier's internal Master Circuit Braker alarmRectifier_X.Alarm_Internal_MCB_FailBraker alarm | Rectifier_X.Alarm_Internal_MCB_Fail | ||||||
16 | Modules Fault | At least one of the available Rectifier modules is not working Rectifier_X.Alarm_Internal_Urgent_RFA || Rectifier_X.Alarm_Internal_NonUrgent_RFA | Rectifier_X.Alarm_Internal_Urgent_RFA || Rectifier_X.Alarm_Internal_NonUrgent_RFA | ||||||
17 | Non Urgent RFA | Rectifier's internal Non Urgent Rectifier Fault alarm | Rectifier_X.Alarm Galooli Non Urgent RFA Alarm Galooli NonUrgent RFA - True if Alarm Internal Non Urgent RFA is true, AND Rectifier_X . Alarm _Galooli_Internal Mains _ Failure is false Rectifier_X.Alarm Galooli Non Urgent RFA True if Alarm Internal Non Urgent RFA is true, AND Rectifier_X.Alarm_Galooli_Mains_Failure is falseAND ((Grid Available And Not Grid Partly Available) or (Generator X On Load)) | ||||||
18 | Non Urgent PFA | Rectifier's internal failure alarm Rectifier_X.Alarm Galooli Non Urgent PFA True if Alarm Internal Non Urgent PFA is true, AND unit's time (UTC + cluster time off set) is between 09:00-15:00 (according to the unit's local time). | Rectifier_X.Alarm Galooli Non Urgent PFA True if Alarm Internal Non Urgent PFA is true, AND unit's time (UTC + cluster time off set) is between 09:00-15:00 (according to the unit's local time). | ||||||
19 | OVP | Rectifier's internal Over Power alarmRectifier_X.Alarm_Internal_OVP | Rectifier_X.Alarm_Internal_OVP | ||||||
20 | PLD | Rectifier's internal Priority Low Differed alarmRectifier_X.Alarm_Internal_PLD | Rectifier_X.Alarm_Internal_PLD | ||||||
21 | Rectifier X Door | At least 1 of the Rectifier Cabinet door is opened Rectifier_X.Alarm__Door | Rectifier_X.Alarm Internal Door Open | ||||||
23 | Surge Protector Fault | At least one of Rectifier_X.Alarm_Internal_SurgeProtection is true | Rectifier_X.Alarm_Internal_SurgeProtection | Rectifier_X.Alarm_Internal_SurgeProtection | |||||
24 | Temp High | Rectifier's internal Temp High alarmRectifier_X.Alarm_Internal_Temperature | Rectifier_X.Alarm_Internal_Temperature | ||||||
25 | Urgent Alarm | At least 1 critical mapped alarm is triggered on the rectifier | Rectifier_X_Alarm_Urgent | Rectifier_X_Alarm_Urgent | 26 | Rectifier_X.Alarm Galooli Urgent PFA True if Rectifier_X.Temperature_Inetrnal > 50 OR Rectifier_X.Module_Temperature_1X > 60 (at least one module meets the condition) OR Rectifier_X.Alarm_Internal_Temperature is true | ectifierthe rectifier | Rectifier_X_Alarm_Urgent | |
26 | Urgent PFA | Rectifier's internal failure alarm | Rectifier_X.Alarm Galooli Urgent PFA True if Rectifier_X.Temperature_Inetrnal > 50 OR Rectifier_X.Module_Temperature_1X > 60 (at least one module meets the condition) OR Rectifier_X.Alarm_Internal_Temperature is true | ||||||
27 | Urgent RFA | Rectifier's internal urgent failure alarm | Rectifier_X.Alarm Galooli Urgent RFA - True if Alarm Internal Urgent RFA is true, AND Rectifier_X . Alarm _Galooli_Internal Mains _ Failure is false Rectifier_X.Alarm Galooli Urgent RFA True if Alarm Internal Urgent RFA is true, AND Rectifier_X.Alarm_Galooli_Mains_Failure is falseAND ((Grid Available And Not Grid Partly Available) or (Generator X On Load)) |