Item

...

Value Type

...

Thresholds

...

Field Meaning and Logic

...

DC Voltage threshold BLV

...

 

...

 

...

DC Voltage threshold BLV Release

...

 

...

 

...

DC Voltage threshold PLD

...

 

...

 

...

DC Voltage threshold PLD Release

...

 

...

 

...

DC Voltage threshold LVD

...

DC Voltage threshold LVD Release

...

The purpose of this section is to describe the global DC alarms.

*In the event that the alarm becomes active, it will remain active until the release threshold value is reached

Item

The Affected Digital Alarm/Dashboards

Default Values

Voltage Threshold LVD

 Site_Global.DC_Alarm_LVD

 

43.5 V

Voltage Threshold LVD Release

 49V

Voltage Threshold BLV

 Site_Global.DC_Alarm_BLV

 48V

Voltage Threshold BLV Release

 50V

Voltage Threshold PLD

 Site_Global.DC_Alarm_PLD

 

 45.5V

Voltage Threshold PLD Release

51V

Voltage Threshold Generator Fail To Start

Site_Global.Generator_X_Fail_To_Start

*Hard coded release - 49.3V

48.3V