Item
...
Value Type
...
Thresholds
...
Field Meaning and Logic
...
DC Voltage threshold BLV
...
...
...
DC Voltage threshold BLV Release
...
...
...
DC Voltage threshold PLD
...
...
...
DC Voltage threshold PLD Release
...
...
...
DC Voltage threshold LVD
...
DC Voltage threshold LVD Release
...
The purpose of this section is to describe the global DC alarms.
*In the event that the alarm becomes active, it will remain active until the release threshold value is reached
Item | The Affected Digital Alarm/Dashboards | Default Values |
---|---|---|
Voltage Threshold LVD | Site_Global.DC_Alarm_LVD
| 43.5 V |
Voltage Threshold LVD Release | 49V | |
Voltage Threshold BLV | Site_Global.DC_Alarm_BLV | 48V |
Voltage Threshold BLV Release | 50V | |
Voltage Threshold PLD | Site_Global.DC_Alarm_PLD
| 45.5V |
Voltage Threshold PLD Release | 51V | |
Voltage Threshold Generator Fail To Start | Site_Global.Generator_X_Fail_To_Start *Hard coded release - 49.3V | 48.3V |