Preparation

Installation Preparation

Please ensure that you have the following items:

  • Sparta gateway

  • Connector for power cables included with Sparta gateway

  • RS485 connector (Connects the Sparta to the RS485 to USB converter)

  • Cable lug. Specifications: insulated ring-type lug. Inner Dia: 6.4mm, stud size: M6, Cable size 0.5-2.5mm

  • Thick double side adhesive. Specifications: Thickness-2mm, width-30cm, material - Nano PU gel

  • If you wish to conceal Sparta inside of the battery box so that it will not be visible, then you will need to bring a special glue/silicone for this purpose

  • Torque wrench

  • Plier

  • Screwdriver

  • Adjustable spanner

  • RS485 To USB Converter& two 0.5mm thick communication cables. The length of the cables is determined by the distance between the RS485 to the USB converter and the computer

Configuration Preparation

  • A computer with an internet connection is required

  • Power Center installed - Click here to download. Credential info can be received from your Account Manager or Galooli support

  • Login credentials for Galooli Solution

  • RS485 to USB converter - Refer here for driver installation instructions.

Battery Connection & Power

Sparta gateway may be mounted either on the battery box or inside it. To be hidden, Sparta must be inserted inside the battery box.

  1. Place the Sparta gateway in the desired location on the battery according to your requirements (outside or inside the battery box).

  2. Connect the Sparta gateway to the battery, connect the red wires to the plus side and the black wires to the minus side.

Outside-the-box connection

Image RemovedImage Added

 

 

Inside-the-box connection

Image RemovedImage Added

 

 

  1. It is now necessary to connect the Sparta gateway to the computer for configuration.

Power Center Configuration

  1. Connect the RS485 connector to the Sparta input.

Pin #

Name

image-20240813-082944.png

1

RS485-A (Red)

2

RS485-B (Black)

3

GND (Yellow) - Inactive

  1. Connect the other side of the RS485 connector to the RS485 to USB converter.

Pin #

Color

RS485 Converter

image-20240813-083356.png

1 - RS485 A

Red

Input 1

2 - RS485 B

Black

Input 2

  1. Connect the RS485 converter to the computer

  2. Open the Power Center

  3. Open the “Active Device” drop-down menu, and select “Power Device”.

  1. Open the “Connect Via” drop-down menu, and select the relevant Serial COM port.

  1. Chose the “Sparta” tab

image-20240807-125421.png
  1. By double-clicking on the "Messages" option, a new tab will be opened with the name "Communication Log". You should drag this tab to the right side of the Power Center until you see a square icon. Locate the computer's mouse in this square and drop the "Communication Log" there. This action will locate the "Communication Log" in a convenient location so that it can be viewed to determine whether there has been communication with Sparta.

    After that, click the “Sparta” tab again.

    Ensure that the "Communication log" is filled with data.

image-20240807-125823.png
  1. Click on “Read Configuration” and then “Status”.

image-20240807-125937.png
  1. If it is necessary to change Sparta’s default parameters, please refer to the following section.

Note

This section describes the changes that are made to Sparta when the user is physically connected to it. In the event that the connection is not physical, but rather via wireless connection (OTA), the Sparta should be set to "Maintenance Mode" in order to make any configuration changes.
https://galooli.atlassian.net/wiki/spaces/KP/pages/2491940865/Sparta+Lead-acid+Battery#Modes

image-20240813-084319.png
  • Server URL
    The address of the Galooli Server for the purpose of transferring data. This information can be found in the technical booklet of the organization.

  • Network APN

    The following is a list of all the global SIM cards that Galooli offers. There will be a different APN for each local carrier.

    SIM card address:

    • Telefónica Digital Solutions - M2M & IoT (telefonica)

    • internet.gma.iot (t-mobile)

    • bicsapn (BICS)

  • Network User
    There are some cellular operators that require a username for each SIM card. In the absence of a mention, move on.

  • Network Password
    There are some cellular operators that require a password for each SIM card. In the absence of a mention, move on.

  • Out of storage voltage [V]
    When a certain voltage is applied, the Sparta will move from the “Storage” mode to the “In Cabinet” mode. 13.1V as a default.

  • Storage Sampling Interval [Minutes]
    During The interval during "Storage" mode , for when the purpose of transmitting Sparta status and location to the system, an interval is set which indicates that the unit will periodically transmit data to the system. By default, the unit will check its own status every 60 minutes and transmit it to the serverSparta will check its own status. During the test, no information is recorded or sent to the server, but only an internal test is conducted. The Sparta uses this method to determine whether it should move to another status set by the user. The default is every 60 minutes.

  • In-Cabinet Metrics Interval [Minutes]
    The duration of Sparta connection to the server during each interval. Only in this period of time, Sparta can be connected via OTA and commands can be sent to the device. However, a serial connection can be made at any time. 5 minutes is the default time.

  • In-Cabinet Wakeup Interval [Hours]
    Sparta battery frequency of connection to the server. In this mode, the Sparta can be connected via OTA and commands can be sent to the device. However, a 24 hours is the default time.
    Note: A serial connection can be made at any time. 24 hours is the default OTA connection can be made only in this period of time.

  • GPS state while in-Cabinet
    The GPS receiver status is controlled while the Sparta is in the "In Cabinet" mode. The Sparta location will not be sent to the server during the "In Cabinet" wakeup interval if the box is unchecked.

  • Report Intervals [seconds]
    Sets how often the Sparta transmits information to the server once the unit is in “Tracking” mode.

    60 seconds is the default time.

  • Movement Sensor Sensitivity
    Defines the Sensitivity level of the accelerometer (motion sensor).
    Normal is the default.

  • Disable User Interface
    TBAIn the event that this option is checked, the Sparta's LEDs will not be illuminated.

  • Enable Silk Route™ Technology
    With this option enabled, Sparta's track trail display on the map will be more accurate and uninterrupted while in "tracking" mode. Consequently, more power and data are consumed.

  1. Ensure that the Sparta hardware version is up-to-date, if necessary update the version. After an upgrade has occurred, click on “Write configuration”.

Image - TBA

Make sure to click on "Write configuration" after setting all the relevant parameters.
Note
Note

Whenever a serial connection is used, the version upgrade must be performed in "Maintenance" mode.
In order to upgrade the Sparta version wirelessly (OTA), you must wait for the Sparta "In Cabinet" interval, connect, switch to maintenance mode, and then upgrade the Sparta version.

Version updates can be performed through the Power Center or through the Galooli Solution.
My Versions

image-20240813-105625.pngImage Added

Galooli Solution Configuration

Organization Tree

Open the Galooli Solution >> Click on the “Manager” application >> Click on “My Units” >> It is recommended that you create meaningful clusters and groups in your organization tree that will assist you in managing all future units. My Units

Unit Configuration

In the event that you own an active Sparta gateway in your organization, you can copy all or part of the configurations to the new Sparta gateway using the "Copy Settings” tool or “Clone Unit” option.

In the event, this is the organization's first Sparta gateway, please continue to the first paragraph.

  1. Find the relevant unit within the "Stock" cluster and click on it. My Unit

  2. The "Overview" tab should be used to give the unit a name, a description, and an asset type. Set the "Stationary Unit" to "No". Set the destination Email and SMS. Email and phone numbers can be set at the cluster or group level as opposed to the unit level. The remainder of the information can be filled in as needed.https://galooli.atlassian.net/l/cp/GUAkk1K4

  3. On the "Events" tab, add the relevant events. https://galooli.atlassian.net/l/cp/zjX0vNmg

  4. Click on “Save

  5. Transfer the unit from the "Stock" cluster to another relevant cluster. https://galooli.atlassian.net/l/cp/J6c4DHE1

  6. Verify that the unit can be seen on the Panorama map and that the Panorama time stamp is being updated. https://galooli.atlassian.net/l/cp/hth1o23t

Info

Please follow the next link if the location of the unit is incorrect or not set at all - https://galooli.atlassian.net/wiki/spaces/KP/pages/2491940865/Sparta+Lead-acid+Battery#Manual-Location-Setup