Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

NOC alarms are a set of alarms developed specifically for the NOC application. Categorizing the alarms into different categories makes it easier for the user to configure them. You can get a good idea of the extreme conditions on site based on the alarms. For the benefit of our customers, Galooli has built each alarm with its own hardcoded threshold. Updates are made to the alarms list on a regular basis.

Panel
panelIconIdatlassian-info
panelIcon:info:
bgColor#57D9A3

System Thresholds - NOC alarms are affected by Galooli "System Thresholds", which can be changed by the user through the Galooli Solution. The NOC alarm types listed below include system thresholds data. https://galooli.atlassian.net/wiki/spaces/KP/pages/2802450433/My+Units#KPIs-Breakdown

Table of Contents

Discrete Inputs

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

Digital 1-10

Alarms related to digital inputs in the system will be triggered only if the digital I/O returns a "True" status.

Note: Alarms will not be triggered if the relevant digital input (1-10) is not configured in My Units → Edit Unit → Configuration → I/O's → Input → Digital.



Digital X

Environment Alarms

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

A/C Fault

At least 1 of the Shelter A/C alarm is active

Shelter_X.Alarm Galooli AirCondition Y

2

AWL Fault

Aviation/Aircraft Warning Light is OFF

Site_Global.Alarm Galooli Aviation Light Fail

3

Fence Alarm

Fence intrusion detection alarm is active

Site_Global.Alarm Galooli Fence

4

Gate Alarm

The alarm is active if at least one of the alarms (Entrance/Fence) is true.

Site_Global.Alarm Galooli Entrance

5

High Temp General

At least 1 shelter temperature is above the set high-temperature threshold

Shelter_X.Alarm Galooli Temperature

  • Shelter X High Temperature Threshold

6

High Temp Shelter X

Temperature is above the set high-temperature threshold

Shelter_X.Alarm Galooli Temperature Very High

7

Intrusion Alarm 

At least 1 of the Shelter Door is Open

Shelter_X.Alarm Internal Door Open

8

Smoke Alarm

At least 1 of the Shelter Smoke alarms is active in 1 or more of the 5 shelters

Shelter_X.Alarm Internal Smoke

9

Very High Temp General

At least one shelter temperature is above the set Very-high-temperature threshold

Shelter_X.Alarm Galooli Temperature

  • Shelter X Very High Temperature Threshold

10

Very High Temp Shelter X

Temperature is above the set Very high-temperature threshold.

Shelter_X.Alarm Galooli Temperature Very High

...

Alarm Number

Alarm Name

Description

System Parameter Name

1

Fuel  Drop

Fuel drop of 10 liters and above. The alarm is deactivated after 1 hour.

The data is recorded and displayed in the Galooli solution until the next drop.

Generator.Fuel Alerts.Last Drop

2

High Level

If Site Global Fuel 1-2/Tank Max Capacity > 0.9. The ‘Tank Max Capacity’ is determined according to the fuel’s calibration table

Site Global Fuel X/Tank Max Capacity

3

Level Low

1 of the fuel level is low

Site_Global.Alarm_Fuel_X_Low

  • Level Low Threshold

4

Level Very Low

1 of the fuel level is very low

Site_Global.Alarm_Fuel_X_VeryLow

  • Level Very Low Threshold

...

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

Generator Fault

At least 1 Generator alarm is on

(Generator_X.Alarm Galooli Active) && !(Site_Global.Alarm Galooli Generator X Fail To Start)

2

Battery High

At least one of Generator_X.Battery_High is true

Generator_X.Alarm Galooli Battery High

  • Battery High Voltage

3

Battery Low

At least one of the generators battery voltage is low

Generator_X.Alarm Galooli Battery Low

  • Battery Low Voltage

4

Charge Alternator Fail

At least one of Generator_X.Charge_Alternator_Fail is true

Generator_X.Alarm Internal Alternator fail

5

Generator Controller Fault

No communication between the Gen controller and Galooli RTU, controller data is not available.

Generator_X.Disconnected

6

Door Open

At least one of Generator_X.Door_Open is true

Generator_X.Alarm Internal Door Open

7

Emergency Stop

Generator Emergency Stop occurred

Generator_X.Alarm Internal Emergency Stop

8

Engine Hours Tampering

The alarm become active when the difference in engine hours eXceeds the difference in records by more than two hours.

It is essential that the NOC alarm is configured with an “Activation Delay time: 0” and a long “Release Delay time” in order to detect the alarm effectively (the above flag will only be True for one transmission of the unit and will be canceled by the time of the neXt transmission).

Generator_X.Alarm Galooli Engine Hours Tampering

9

Generator Fail To Start

  • For hybrid sites: the alarm will be active when DC voltage (Site Global.U_System) ≤ Generator fail to start threshold and Gen is “off” and another power source not available.

  • For non-hybrid sites: the alarm will be active if “Site_Global.AC_Fail” is “True”, or “Generator_1.Fail_To_Start” is “True” (reading from the generator panel)

Site_Global.Alarm Galooli Generator X Fail To Start

  • Voltage Threshold Generator Fail To Start

10

Generator Fail To Stop

Grid available and Generator is running or Generator_1.Fail_To_Stop is true (reading from the generator panel)

Generator_X.Alarm Internal Fail to stop

11

High Coolant

Generator High Coolant indication

Generator_X.Alarm Internal High Coolant

12

Low Coolant

At least one of Generator_X.Low Coolant is true

Generator_X.Indication Internal Low Coolant

13

High Load Power

At least one of 'Site_Global.Generator_1-2_High_Load' is true.

Site_Global.Alarm Galooli Generator X High Load

14

Very High Load Power

At least one of 'Site_Global.Generator_1-2_Very_High_Load' is true.

Site_Global.Alarm Galooli Generator X Very High Load

15

High Voltage

Generator High Voltage indication

Generator_X.Alarm Galooli High Voltage

  • Output High Voltage Threshold

16

Low Voltage

Generator Low Voltage indication

Generator_X.Alarm Galooli Low Voltage

  • Output Minimal Voltage Threshold

17

Low Oil Pressure

Generator Low Oil Pressure Indication

Generator_X.Alarm Galooli Low Oil Pressure

18

Not in Auto

Generator Not in Auto mode

Generator_X.Alarm Galooli Not in Auto

19

Over Frequency

Generator Over Frequency indication

Generator_X.Alarm Internal Over frequency

20

Under Frequency

At least one of Generator_X.Under_Frequency is true

Generator_X.Alarm Internal Under frequency

21

Running > 10 Hours at Solar Hybrid Site

The site is running on generator more that 10 hours strait and this is a solar hybrid site

Time In Status

Site Layout

22

Running When Grid Available

Gen is running and Grid is available simultaneously for at least 25 minutes

Time In Status

Site_Global.Grid Available

...

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

AC Meter Grid Disconnected

When AC_Meter_Grid.Disconnected = True, this alarm will activated

AC_Meter_Grid.Disconnected

2

ATS Meter Disconnected

No communication between ATS Meter and the Galooli RTU

AC_Meter_ATS.Disconnected

3

Backup Low Voltage

Backup Voltage < 3.3V

4

Extension Disconnected

One of the eXtensions is disconnected

Site_Global.EX20ETH_X_Disconnected || Site_Global.EX20_X_Disconnected

5

Fuel Sensor Disconnected

No communication between the Fuel sensor and the Galooli RTU

Site_Global.Fuel_X_Disconnected

6

Output Active

TBA

Site_Global.Output_Active

7

Temperature Sensor Fault

The temperature sensor in at least 1 of the shelter is out of range, mostly not real

(Shelter_X.Room_Temperature > 55) || (Shelter_X.Room_Temperature < 0)

8

Tenant 1 - 20
Meter Disconnected

At least 1 of the 20 Tenant meters is currently Disconnected

Tenant_X.Disconnected

9

Unit Disconnected

No communication between Galooli RTU and the server

Status = Disconnected

...

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

AC Meter Grid Low PF

In order to ensure that there are no false alarms regarding the AC meter grid low power factor at least in one phase, the system checks that the PF is greater than 0 and the current of the phase is higher than 1.

  • 0 < ABS(AC_Meter_Grid.PF_LX) < 0.8 (The absolute value of the power factor is greater than 0 and less than 0.8)

AND

  • ABS(AC_Meter_Grid.I_LX) > 1[A] (The absolute value of the current is greater than 1)

2

Battery High Current

The alarm is true if the digital 'Site Global Alarm High Battery Current' is true.

Site_Global.Alarm Galooli High Battery Current

  • High Battery Current Threshold


3


BLV Alarm 

This is a DC voltage threshold - the system will trigger a Battery Low Voltage alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold - Section: Global DC


Site_Global.Alarm Galooli DC BLV

  • Voltage Threshold BLV

  • Voltage Threshold BLV Release

4

Consumers' Load Drop

If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active.

As soon as the site consumption falls below 50% of the average for the previous seven days, this alarm will be activated (the average is updated every night according to the summary report).

 If (Unit KPI Field)‘Consumers Load Drop Current Threshold'> 0, check if 'Site Global Consumers Load Power' < (Site Global U System’ * threshold

Site_Global.Alarm Galooli Consumers Load Drop

  • Consumers Load Drop Current

5

Consumers Load High 

The alarm is true if 'Site Global Consumers Load Power' > threshold, and threshold > 0.

Threshold - unit KPI → Consumers → ‘High Consumers Power Threshold

Site_Global.Consumers_Load_Power [W]

  • High Consumers Power Threshold

6

Generator Running > 3 Hours

The alarm is intended to ensure that there is a logical reason for the generator to run longer than three hours.

In order to obtain information about more than three hours, you must change the Activation Delay time - https://galooli.atlassian.net/wiki/spaces/KP/pages/2483945485/Galooli+NOC+Application#Add-Alarm

Time is status > 3 hours

7

Generator running and battery discharging

The Generator running but battery is discharging

Site_Global.Alarm Galooli Generator Running Battery Discharge

8

Generator Running and Battery not Charging

If site is hybrid AND ‘Site Global.Generator_1-2_Running’ AND ‘Site Global.Battery Charging’ is false

Site Global.Generator_X_Running
and
Site Global.Battery Charging

9

Grid High Current

Thealarm is true if for at least one phase ABS(Site Global Grid_I1-3) > threshold, and threshold > 0.

Threshold - unit KPI → Grid → 'High Current Threshold

Site Global Grid_I1-3 > threshold, and threshold > 0.

10

Grid High Voltage

Will be active if the global Gird_High_Voltage digital/alarm is active. When the voltage of at least one of the phases of the grid exceeds the threshold value configured for the unit in Device Configuration (260V by default), the digital becomes active.
Section: Grid*

Side Global Alarm Galooli Gird_High_Voltage

  • High Voltage Threshold

11

Grid Partly Available

Grid only partly available indication - https://galooli.atlassian.net/wiki/x/CwDYt

Site_Global.Alarm Galooli Grid Partly Available

12

High System DC Voltage

The alarm is true if the digital 'Site Global Alarm High System Voltage’ is true.

Site_Global.Alarm Galooli High System Voltage

  • High System Voltage Threshold

13

 

LVD  Alarm 

This is a DC voltage threshold - the system will trigger a Low Voltage Disconnect alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold. Section: Global DC

At this voltage, the rectifier disconnects all loads to prevent battery deep discharge or damage.

Site_Global.Alarm Galooli DC LVD

  • Voltage Threshold LVD

  • Voltage Threshold LVD

 

14

No Mains

Grid is currently not available

If Grid Fail is True and Site_Global.Is_Planned_Grid_Fail is False

https://galooli.atlassian.net/wiki/x/CwDYt

Site_Global.Grid_Fail

&&

Site_Global.Is_Planned_Grid_Fail

15

 No AC Load

 No AC power to the Rectifier

Site_Global.AC_Fail

||

(

Non Hybrid

&& 

(AC_Meter_ATS.Configured) && !(AC_Meter_ATS.Disconnected && (AC_Meter_ATS.I_LX=0)

||

(AC_Meter_Grid.Configured) && !(AC_Meter_Grid.Disconnected && (AC_Meter_Grid.I_LX=0)

)

16

Other on Load

Galooli RTU can not determine the Site power source

Site_Global.Other On Load

17

 

PLD Alarm 

This is a DC voltage threshold - the system will trigger a Partial Load Disconnect) alarm if the Rectifier, Battery, or Smart Battery Voltage is below that threshold.

At this voltage, the rectifier begins disconnecting none essential Loads to save battery energy for essential loads.
Section: Global DC

Site_Global.Alarm Galooli DC PLD

  • Voltage Threshold PLD

  • Voltage Threshold PLD Release

18

Power Supply Failure

No power to Galooli RTU

External Voltage < 9V

19

Site on Batteries

The site is currently powered by Battery

Site_Global.Alarm Galooli Battery On Load

20

Smart Batteries Alarm Active

At least 1 smart battery alarm is active

Smart_Battery_X.Alarms are not blank, 0 or indicator

21

Smart Batteries Disconnected 

At least 1 of the Smart Batteries is currently not communicating with the Galooli RTU

 Smart_Battery_X.Disconnected

22

Tenant load drop

If Tenant_X.I_L1+2+3 < 50% of Tenant X Average Current then the alarm active
As soon as the tenant's consumption falls below 50% of the average for the previous seven days, an alarm will be generated (the average is updated every night according to the summary report).

Tenant X Alarm Galooli Load Drop

...

Alarm Number

Alarm Name

Description

System Parameter Name

System Thresholds

1

Non-Urgent

At least 1 critical mapped alarm is triggered on the rectifier

Rectifier_X.Alarms Non Urgent

2

AC Surge Protector Fault

At least one of Rectifier_X.Alarm_AC_SPD_Fault is true

Rectifier_X.Alarm Internal AC SPD Fail

3

Alarms Suppressed

It is an alarm from the rectifier that indicates that other alarms have been configured not to be active, leading to alerts not being received by the user.

Rectifier_X.Alarm Internal Suppressed Alarms

4

Battery Alarm

Rectifier's internal battery alarm

Rectifier_X.Alarm Internal Battery

5

Battery Door Open

At least one of 'Rectifier_X.Alarm_Battery_Door' is true

Rectifier_X.Alarm Internal Battery Door Open

6

BLV

Rectifier's internal battery low voltage alarm

Rectifier_X.Alarm Internal BLV

7

Critical Alarm

At least 1 critical mapped alarm is triggered on the rectifier but not internal main failure

(Rectifier_X.Alarm_Critical) && ! (Rectifier_X.Alarm_Internal_Mains_failure)

8

DC Surge Protector Fault

At least one of Rectifier_X.Alarm_DC_SPD_Fault is true

Rectifier_X.Alarm Internal DC SPD Fail

9

Disconnected

No communication between the rectifier panel and the Galooli RTU

Rectifier_X.Disconnected

10

High Battery Temp 

Rectifier's internal High Battery Temp  alarm

Rectifier_X.Alarm Internal Battery Temperature

11

HW Failure

Rectifier's internal HW Failure alarm

Rectifier_X.alarm_Internal_HW_failure

12

Load Breaker

Rectifier's internal Load Breaker alarm

Rectifier_X.Alarm_Internal_Load_Breaker

13

LVD

Rectifier's internal Low Voltage Disconnect alarm

Rectifier_X.Alarm_Internal_LVD

14

Mains Failure

Rectifier's internal Mains Failure alarm

Rectifier_X.Alarm_Internal_Mains_failure

15

MCB

Rectifier's internal Master Circuit Braker alarm

Rectifier_X.Alarm_Internal_MCB_Fail

16

Modules Fault

At least one of the available Rectifier modules is not working

Rectifier_X.Alarm_Internal_Urgent_RFA

||

Rectifier_X.Alarm_Internal_NonUrgent_RFA

17

Non Urgent RFA

Rectifier's internal Non Urgent Rectifier Fault alarm

Rectifier_X.Alarm Galooli Non Urgent RFA

Alarm Galooli NonUrgent RFA - True if Alarm Internal Non Urgent RFA is true, AND Rectifier_X Alarm Internal Mains Failure is false AND ((Grid Available And Not Grid Partly Available) or (Generator X On Load))

18

Non Urgent PFA

Rectifier's internal failure alarm

Rectifier_X.Alarm Galooli Non Urgent PFA

True if Alarm Internal Non Urgent PFA is true, AND unit's time (UTC + cluster time off set) is between 09:00-15:00 (according to the unit's local time).

19

OVP

Rectifier's internal Over Power alarm

Rectifier_X.Alarm_Internal_OVP

20

PLD

Rectifier's internal Priority Low Differed alarm

Rectifier_X.Alarm_Internal_PLD

21

Rectifier X Door 

At least 1 of the Rectifier Cabinet door is opened

Rectifier_X.Alarm Internal Door Open

23

Surge Protector Fault

At least one of Rectifier_X.Alarm_Internal_SurgeProtection is true

Rectifier_X.Alarm_Internal_SurgeProtection

24

Temp High

Rectifier's internal Temp High alarm

Rectifier_X.Alarm_Internal_Temperature

25

Urgent Alarm

At least 1 critical mapped alarm is triggered on the rectifier

 Rectifier_X_Alarm_Urgent

26

Urgent PFA

Rectifier's internal failure alarm

Rectifier_X.Alarm Galooli Urgent PFA

True if Rectifier_X.Temperature_Inetrnal > 50 OR Rectifier_X.Module_Temperature_1X > 60 (at least one module meets the condition) OR Rectifier_X.Alarm_Internal_Temperature is true

27

Urgent RFA

Rectifier's internal urgent failure alarm

Alarm Galooli Urgent RFA - True if Alarm Internal Urgent RFA is true, AND Rectifier_X Alarm Internal Mains Failure is false AND ((Grid Available And Not Grid Partly Available) or (Generator X On Load))

...