Output Global Timeout [Sec]
With the Output Global Timeout parameter, you can specify how long the Elara will wait after the output activation command has been triggered before it deactivates the output. The timeout can be used to specify the duration of the relay activation and can be set to a variety of values.As an example:
When the relay is used to control a motor, the output timeout can be set to keep the motor running for a certain period of time before turning it off.Port-1&2 Modes
Determining the type of RS485 communication between the computer, Elara, and other RS485 sensors.
The different modes are:Host - Used to connect RS485 sensors and third-party devices
Terminal - Galooli's internal use only
Binary - Used to connect Galooli gateways and software such as EX20 and Power Center
Gateway - Galooli's internal use
By default, port 2 mode is used as "binaryā€¯.
Port-1&2 Default Baudrates
There are different frequencies of the units that need to be set properly and appropriately.
The different baudrates are:2400
4800
9600
14400
19200
38400
57600
115200
The default baudrates in port 1&2 are usually 19200
Keep Connection LOG
Saving modem log (communication log and not device operational log).To be used only when necessary to investigate communication/network issues.
LTE Only Mode
When checked, this feature ensures that the Elara will only work with 4G cellular networksIPV6 Mode
If Elara must receive an IP address under IPV6 rather than IPV4. It is necessary to mark the IPV6 mode parameter. There is no need to use it unless there is a special requirement.Extended Report Retries
By default, the Elara gateway transmits a message and repeats it up to five times if the server does not confirm that the message has been received correctly. In some geographical locations, this can be due to network behavior or other network failures. After 5 attempts the message will be erased and Elara gateway will continue to the next message.When such circumstances arise, it is possible for Elara to continue to send a message up to 250 times before deleting it.
It is not recommended to use this parameter. When there is a known problem with the SIM's reception, data usage may increase significantly.
Report Location (GPS)
As soon as the parameter is set, the Elara will report GPS data as part of the standard status message.This option should only be used when necessary due to the following reasons:
Increasing the amount of data transmitted over the network.
There may be jittering at the site location as a result.
Manual GPS location requests can still be made using the "Information" button. When a manual request is made, the device location is forcibly set to the request result, as opposed to the status message, which is based on 'stationary logic'.
CAN Silent Mode
In this mode, Elara CAN prevents data from being sent to the engine control unit, whether it is a direct connection to the engine or a connection to the generator panel.
This mode can therefore be activated if the user wishes to have the unit only "listen" to the communication line.
As this mode may affect the connectivity between the CAN and the unit, it is not Galooli default.
...