Field Name

Field Description

Calculation Method

Tenant X Initial [KWH]

The first record of the kWh value that was read from the tenant's meter, for the selected time range.





Based on the field Colo_Meter_X.Total_KWH [KWH]

Tenant X Final [KWH]

The last record of the kWh value that was read from the tenant's meter, for the selected time range.

Tenant X Total [KWH]

The total energy consumption (kWh) of the tenant, is based on the readings from the tenant's meter.

Tenant X Total DG [KWH]

The total energy consumption (kWh) of the tenant that was received from the generator, is based on the readings from the tenant's meter.

Based on the field Colo_Meter_X.Total_DG_KWH [KWH]



Tenant X Total Non-DG [KWH]

The total energy consumption (kWh) of the tenant that was not received from the generator, is based on the readings from the tenant's meter.

Based on the fields Colo_Meter_X.Total_KWH [KWH],


Colo_Meter_X.Total_DG_KWH [KWH]

Tenant X Assignment

The assignment (name) of tenant X.

Tenant X Min/Max/Avg Current [A]

The minimum, maximum and average current of the tenant's meter.

Tenant X Min/Max/Avg Voltage [V]

The minimum, maximum, and average voltage of the tenant's meter.




Tenant X Power Availability

The total time in the day (hours) the tenant's "Power Down" alarm was false, meaning the tenant received voltage.

Based on records where Colo_Meter_X_Alarm_Power_Down = No.

At the end of the document, there are comments regarding availability.



Tenant X Load Availability

The total time in the day (hours) the tenant's "Load Down" alarm was false, meaning the tenant received current.



Tenant X Accumulated Consumption [KWH]

The calculated energy consumption (kWh) of the tenant, is based on voltage and the current provided to the tenant.

Based on the fields Colo_Meter_X.V_LY [V], Colo_Meter_X.I_LY [V]

X=1->20, Y=1->3

...