DeepSea (DSE) General Configuration Process

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 2 Current »

There are some DSE models that require a special adapter in order to connect to the Galooli gateway. Follow the next link to determine if your model requires this adapter - https://galooli.atlassian.net/l/cp/jN7a0Gt0

Power Center Configuration

  1. Open the Powe Center.

  2. Open the “Active Device” drop-down menu, and select “Elara”.

  3. Open the “Connected Via” drop-down menu, and select “Serial COM X

  4. Navigate to the “Elara” tab.

     

  5. Navigate to the “Configuration” tab.

  6. Click the “Read Configuration” button.

    7. In the “Configure” tab click the “Add Port 1 Device”.

    8. The “Elara – Modbus Device Configuration” window will pop up, select the “Generator” device and the relevant module of the DSE controller and the phase.

    Ensure that the physical device ID is - 10 and the baudrate is 19200.

    Apply the changes.

    9. Click the “Write Configuration” button to save the changes.

    10. Click the “Reset” button.

    11. Navigate to the “Status” tab to view the status of the DG controller.

Web Solution Configuration

  1. Open the Galooli Web Solution

  2. Select the “Manager” Solution >> “My Units” menu

  3. Click on the relevant unit in the organization tree

  4. Select the “Configuration” tab >> “Device Configuration” sub-tab

  5. Select the “Section: Generators” >> check the “DG X” relevant panel

 

 