Detailed Report Use Case

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 4 Current »

The Request

You received an email notification from the Galooli system regarding an on-gird not hybrid site that contains a generator. This notification was caused by an event called “Site on batteries”. It is your responsibility to investigate why the site worked on batteries when that is not the natural power source of this site.

This situation may be caused by one or more of the following factors:

  • There is no grid connection and the generator is not automatically started to run

  • The generator battery level is low there for the generator fail to start

The Solution

  1. Open the Galooli Pro Application.

  2. To create a full site status map, add the following fields:

    • Add a “Recorded Analog Inputs” >> "Site_Global.Grid_Available" field, which indicates when the grid is no longer available.

    • Add a “Recorded Digital Inputs >> Site_Global.Generator_X_Running” field, which indicates the status of the generator.

    • Add a “Recorded Digital Inputs >> Site_Global.Battery_Discharging” field, indicating whether the battery is discharging.

    • Add a “Recorded Digital Inputs >> Site_Global.Generator_X_Fail_To_Start” field, which indicates that the generator has failed to start.

    • Add a “Recorded Analog Inputs >> Generator_X.Battery_Level [V]” field, which indicates the current battery level of the generator.

    • Add a “Recorded Analog Inputs” >> “Generator_X.Not_in_AutoMode” field, which indicates if the generator's working mode is not "Auto".


3. Use the "Detailed Graph" view in order to gain a full understanding of the site's operational status and in order to determine why the site operated on batteries when it was not supposed to.

As you can see in the graph below,