Skip to end of banner
Go to start of banner

Carlo Gavazzi EM24

Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 19 Next »

The AC Meter is a three-phase electrical isolation transducer.

Features

  • Three-phase energy analyzer

  • RS485 communication port

  • Easy installation

  • Support high current CT rings

Technical Specification

Power Supply

Self powered

Rated Voltage

400V LL AC

Rated Current

65A

Rated voltage L-N

113V to 265 V LN

Rated voltage L-L

196V to 460 V LL 

Technical Specifications

 EM24 Direct Pinout Diagram

Pin number

Description

1

PHASE 1 Voltage (input)

3

PHASE 1 Voltage (output)

4

PHASE 2 Voltage (input)

6

PHASE 2 Voltage (output)

7

PHASE 3 Voltage (input)

9

PHASE 3 Voltage (output)

11

N

41

RS485 B (Labeled A-)

42

RS458 A (Labeled B+)

43

GND

 

EM24 CT Ring Pinout Diagram

Pin number

Description

1

PHASE 1 Voltage (input)

3

PHASE 2 Voltage (input)

5

PHASE 3 Voltage (input)

7

N

8

CL1+

9

CL1-

10

CL2+

11

CL2-

12

CL3+

13

CL3-

55

0V

57

220V

41

RS485 B (Labeled A-)

42

RS458 A (Labeled B+)

43

GND

Recommended Configuration for Galooli Gateways

  • Recommended Galooli gateways:

Elara

Corona

  • Power Center recommended configuration

  • No labels