Field Name | Field Meaning and Logic |
---|
Engine Hours Tampering
| The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours. [2 < (ABS(engine hours difference - time difference]. The unit will display an alert if such a situation occurs. Additionally, when the above flag is set to true, an alert will appear on the NOC application. The alert will only be active at the time of the unit's transmission. In order to receive an effective alert in the NOC application - set the alert without an “Activation Delay Time”, and set a sufficient “Release Delay Time” (so that the alert does not close automatically too quickly). The alert will be applied only to units with a generator panel installed (not applicable to units without a generator panel).
|
Load Power | This is the direct reading of the power value from the generator. |
Gen PF1-3 (Power Factor)
| The Power Factor will be filled with a default value of 0.95 if there is no power factor for the phase and no direct reading of power, voltage, and current (all three). |