Field Name

Field Meaning and Logic




Engine Hours Tampering

The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours.
[2 < (ABS(engine hours difference - time difference]. The unit will display an alert if such a situation occurs.

  • Additionally, when the above flag is set to true, an alert will appear on the NOC application.

  • The alert will only be active at the time of the unit's transmission. In order to receive an effective alert in the NOC application - set the alert without an “Activation Delay Time”, and set a sufficient “Release Delay Time” (so that the alert does not close automatically too quickly).

  • The alert will be applied only to units with a generator panel installed (not applicable to units without a generator panel).

Load Power

This is the direct reading of the power value from the generator.


Gen PF1-3 (Power Factor)

The Power Factor will be filled with a default value of 0.95 if there is no power factor for the phase and no direct reading of power, voltage, and current (all three).