Field Name

Field Meaning and Logic




Engine Hours Tampering

The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours.
[2 < (ABS(engine hours difference - time difference]. The unit will display an alert if such a situation occurs.

  • Additionally, when the above flag is set to true, an alert will appear on the NOC application.

  • The alert will only be active at the time of the unit's transmission. In order to receive an effective alert in the NOC application - set the alert without an “Activation Delay Time”, and set a sufficient “Release Delay Time” (so that the alert does not close automatically too quickly).

  • The alert will be applied only to units with a generator panel installed (not applicable to units without a generator panel).



Gen PF1-3

  • Direct read of the total power

  • Sum of the power of each phase:

    • Direct read of phase power

    • phase voltage * current * power factor (0.95 as default)

Load Power