The Ex20 extension enables the expansion of Elara connectivity and can be connected to Techbase via Modbus.

With the Ex20 connected to the Elara tray/metal box, a greater quantity of analog and digital sensors may be connected to the Elara.

Features

  • 4 analog input (0-5V)

  • 8 analog input (0-15V)

  • 5 Digital inputs (Negative)

  • 1 Open collection output

  • 1 RS232 Gateway

Hardware Specifications

Power Supply

9 - 30 V

Power Consumption

Full power mode

0.12 W average (Aprox.)

@12v aprox. 10mA

General purpose inputs

12 Analog inputs (0-5v / 0-15v available – Model specific)

8 digital inputs (Model specific)

Outputs

Open collector output (Model specific)
SSR dry contacts (Model specific)

Serial Communication

RS485 (Main)

RS232 (Model specific)

CAN (Model specific)

RS485 (Secondary – Model specific)

Storage Temperature

-40 - 85 Celsius

Working Temperature

-20 - 70 Celsius

Max. Relative humidity

90%

Weight

80g (Aprox.)


Output specifications

Output Type

Open Collector

Max. Continuous working current

200 mA

Over Current protection

300 mA (Aprox.)

Maximum working voltage

40 V


General-purpose analog inputs specifications

Reading Voltage range

0-5V / 0-15V

Reading Resolution

2 mV / 5mV

Reading Accuracy (max error)

2%

Max input voltage

40V


Negative digital inputs specifications

Low level threshold (Active)

1 V

High Level threshold

1.4V


Mechanical Dimensions

Length

86mm

Width

70mm

Height

58mm

Pinout

0-5V

0-5V

0-5V

0-5V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

0-15V

GND

PWRIN

RS485-A

RS485-B

DIG1

DIG2

DIG3

DIG4

RS232-TX

RS232-RX

DIG7

OUT

 Status LEDs

Active state

Blinking pattern description

Pattern

Host Connected

Green, Fast blink (for a period of 10 Sec after each message from host)

 

Gateway mode: No host, but data received at the RS232 port

Red, Fast blink (for a period of 10 Sec after each message from host)

 

Idle State (No communication)

Red, short blink and long pause.

Idle State (No Communication), Error condition

Red, (X>1) Short blinks and long pause.

Contact Galooli for detailed description on detection of fault state

 

 

 Pinout

Pin#

Name

AN1

Analog 1

AN2

Analog 2

AN3

Analog 3

AN4

Analog 4

AN5

Analog 5

AN6

Analog 6

AN7

Analog 7

AN8

Analog 8

AN9

Analog 9

AN10

Analog 10

AN11

Analog 11

AN12

Analog 12

IN-

GND - Terminal Blocks Power

IN+

+12V DC - Terminal Blocks Power

RS485 A

RS485 A Comuunication pin

RS485 B

RS485 B Comuunication pin

DIG1

Digital 1

DIG2

Digital 2

DIG3

Digital 3

DIG4

Digital 4

RS232 TX

RS232 transmitted data

RS232 RX

RS232 received data

DIG7

Digital 7

OUT

Output