Name of the lesson

AC meters and AC Current Transformer Rings

Purpose of the lesson

During this lesson, you will learn how to choose the correct AC meter and current transformer ring for your site

Target Audience

Service providers, back-office, organization managers, technicians, etc.

What to expect at the end of the lesson

The user will acknowledge:

  • Which AC meters and Current Transformer Rings does Galooli provide

  • Which AC meters are suitable for which Current Transformer Rings

  • How to choose the perfect AC Meter and Current Transformer Ring for my site

  • How accurate are the AC Meter and the AC ring

  • How to install the AC meters and Current Transformer Rings on site

It is highly recommended to go through the contents in the order in which they appear

Which AC meters and Current Transformer Rings does Galooli provide?

Galooli supports a variety of AC meters and Current Transformer Rings according to the changing needs of the users, different currents, amount of phases, conversion ratio, and the diameter of the AC cables.

The meters can include an entry for the AC cable or meters that require the use of Current Transformer Rings.

Current Transformer Rings can be used with cables of varying diameters, some of which have an open and close mechanism.

Which AC meters are suitable for which Current Transformer Rings?

(tick) CE Transducer CE42 AC meter works without any Current Transformer Ring however, the cable entry can
be too narrow for some cable's diameter.

(tick) CE Transducer CE42CT AC meter works best with the CE-CTH Split Core rings. Specifically with the rings
that has a conversion ratio of 1A

(tick) Carlo Gavazzi EM210 AC meter works best with the Rogowski CT rings.

How to choose the accurate AC Meter and Current Transformer Ring for my site?

There are a couple of questions you should answer to choose the most suitable AC Meter and Current Transformer Ring:

  • What is the current that needs to be measured?

  • How many phases does the energy source have?

  • What is the conversion ratio?

  • What is the diameter of a cable that needs to be measured?

    The following table allows you to easily choose the required products.
    Catalog numbers are internal to Galooli.

Ring Diameter/Current

≤ 30A

≤ 50A

≤ 150A

≤ 200A

≤ 4000A


≤ 11 mm

CE42

400-ACMetAJ42B-502

No Current Transformer Ring needed


(error)



≤ 24 mm

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin24H30A1A-502

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin24H50A1A-502

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin24H150A1A-502


(error)



(error)



≤ 36 mm

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin36H30A1A-502

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin36H50A1A-502

CE42CT
400-ACMetCE42CT-502
+
CE-CTH
400-AcRin36H150A1A-502


(error)


(error)



≤ 350 mm

Carlo Gavazzi EM210
400-EM210HICU-502
+
Rogowski
400-AcRog350-502



≤ 600 mm

Carlo Gavazzi EM210
400-EM210HICU-502
+
Rogowski
400-AcRog600-502



≤ 900 mm

Carlo Gavazzi EM210
400-EM210HICU-502
+
Rogowski
400-AcRog900-502

How accurate are the AC Meter and the AC ring?

Item Codes/Data

Meter
Accuracy

Ring
Accuracy

Accuracy
Calculation

Calculation
Examples

Galooli Item Code

Voltage reading accuracy

Current reading accuracy

CT Accuracy

Overall voltage accuracy

*Overall current accuracy

*Overall kwh
accuracy

Input voltage

Voltage-

Voltage+

Input current

Current-

Current+

Kwh

Kwh-

Kwh+

400-ACMetCE42CT-502 (Meter)

0.50%

0.50%

Not relevant

400-AcRin24H30A1A-502 (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

230

227.5

232.5

150

-148.5

+151.5

200

-197

+203

400-AcRin24H50A1A-502 (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

230

227.5

232.5

50

-49.5

+50.5

200

-197

+203

400-AcRin24H150A1A-502 (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.00%

230

227.5

232.5

30

-29.55

+30.45

200

-196

+204

400-AcRin36H30A1A-502 (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

230

227.5

232.5

150

-148.5

+151.5

200

-197

+203

400-AcRin36H50A1A-502 (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

230

227.5

232.5

50

-49.5

+50.5

200

-197

+203

400-AcRin36H150A1A-502 (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.00%

230

227.5

232.5

30

-29.55

+30.45

200

-196

+204

**400-ACMetAJ42B-502 (Meter)

0.50%

0.50%

Not relevant

1.00%

230

225

235

200

-199

+201

200

-198

+202

***400-AcRin150A5A-502 (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.00%

230

228.8

231.2

150

-147.75

+152.25

200

-196

+204

***400-AcRin50A5A-502 (Ring)

0.50%

0.50%

3.00%

0.50%

3.50%

4.00%

230

228.8

231.2

50

-44.75

+55.25

200

-192

+208


*Overall current accuracy = Meter current reading accuracy + CT Accuracy

*Overall kwh accuracy = Overall voltage accuracy + Overall current accuracy

**The meter can measure current and voltage without a CT ring

***These rings are not available for sale

What is the best way to install the AC meters and Current Transformer Rings on site?

The installation process of the AC Meter and Current Transformer Ring needs to be accurate and in the right order for the current measurement will be correct.

You will find a lot of important information about the AC Meter and Current Transformer Ring installation process in the “Read more” section.