The DC Meter is a split-core current measurement of DC power.

  • DC Multi-parameter monitoring, U, I, P, KWH

  • Various models for various measure range for option:

  • Current: 0-500A~300ADC (100A & 500A)

  • Voltage: 0-1000V (60V & 1000V)

  • Energy data power failure protection

  • Bi-direction detection for U, I, P, KWH

  • Work with a wide range of power sources, +9V~+24V

  • High stability, 2KV surge protection on input, power supply, and output interface

Technical Specification

Temperature Range (operating)

-10°C – +5°C

Measuring range

0~50-500ADC, 0-1000VDC

Baud rate

19200, 9600(default), 4800, 2400, 1200

Isolation voltage

2500 V DC

Temperature drift

≤1000ppm/°C

Output

DC voltage, DC current, DC power and energy

Meter voltage reading accuracy

(Same for both transducers)

±0.2%

Meter current reading accuracy
(Same for both transducers)

±1%

Overall kwh accuracy
(Same for both transducers)

±1.20%

Technical Specifications

  • Manufacturer's website - SSET

Model

Manufacturer PN.

Galooli PN.

Manufacturer Datasheet

Energy DC Meter CE11 60V*100A

CE-AD11B-34GS4-1.0/60V*100A

400-DCMultMtr-516 (Old Version)

 

 

Energy DC Meter CE11 60V*100A

CE-AD11D-34GS4-1.0/60V*100A

401-DCMultMtr-516 (New Version)

Energy DC Meter CE11 60V*500A

CE-AD11D-34GS4-1.0/60V*500A

401-DCMultMtr-500A

Energy DC Meter CE11 1000V*100A

CE-AD11B-34GS4-1.0/1000V*100A

400-DCMultMtrHigh-516

  • Test Report

Pinout Diagram

Pin#

Name

1

Voltage measure (+)

4

Voltage measure (-)

5

POWER (12V)

6

GND (-12V)

8

RS485 B

9

RS485 A