Field Name

Field Meaning and Logic


Generator_X.Engine_Hours_Tampering

The digital field becomes "True" when the difference in engine hours exceeds the difference in records by more than two hours.
[2 < (ABS(engine hours difference - time difference].

Rectifier_X.Alarm_Surppressed

It is an alarm from the rectifier that indicates that other alarms have been configured not to be active, leading to alerts not being received by the user.

Site_Global.Alarm Galooli Generator X High Load

Site_Global.Alarm Galooli Generator X Very High Load

Site_Global.Alarm Galooli High Battery Current

The alarm will be activated if the unit is set to "Global DC.High Battery Current Threshold" AND "Site_Global.Battery_Current [A] > Global DC.High Battery Current Threshold"

Site_Global.Alarm Galooli High System Voltage

The alarm will be activated if the unit is set to “Global DC.High System Voltage Threshold” AND “Site_Global.U_System [V] > Global DC.High System Voltage Threshold”

Rectifier_X.Alarm Internal Solar SPD Fail