The Generator card illustrates how the generator is used on the site.

The Generator card will appear on the screen only if Generator_1.Configured is true Or Fuel_1. Configured is true, or Configurations->DG1 Running is true.

Main View

  • "On/Off" sign - green and "On" if the generator is running, yellow and "Off" otherwise. If the device is disconnected, the text will be according to Site_Global.DG_Running (On/Off), but the color will be gray.

  • Alarms indication and number (for the list of alarms see Expand) - the color of the alarm bar will be the color of the most critical alarm.

    • Fuel Level (Site Global Fuel 1) - Colors for the fuel data:

    • Orange (urgent alarm) If Site_Global_Fuel_1_Low is true

    • Red (critical alarm) If Site_Global_Fuel_1_VeryLow is true

  • If Fuel_1_Disconnected is true, the disconnected icon will appear next to the Fuel Level title, and the color of the value will be gray.

  • Load - DG1_Load_Power

  • Working Mode (Generator_1.Working_Mode)

    • Color based on Generator1.Not_in_AutoMode - (Urgent-Orange)

Expanded View

  • The fuel level, load, and world mode are the same as in the main view.

  • Control button - clicking the control will open a drop-down with the options:

    • Engine Start, Engine Stop - Use the generator control panel to start and stop the generator

    • Auto Mode, Stop Mode, Manual Mode

    • Test On Load Mode

    • Alarms Reset, and Alarms Reset 2

    • Output - On, Output - Off - Use the Elara gateway output to start and stop the generator.

After clicking one of the options, a confirmation message will appear as a popup. "Are you sure? The selected command will be applied to the generator".

  • Engine Hours - Generator_1.Engine_Hours

  • Coolant Temp (Generator_1.Coolant Temp)

    • Color based on Generator1.High_Coolant (Urgent-Orange), Low_Coolant (Non-Urgent-Yellow)

  • Battery Level (Generator_1.Battery_Level)

    • Color if Generator1.Battery_High Or Generator_1.Battery_Low (Urgent-Orange)

  • Oil Pressure - (Generator_1.Oil Pressure)

    • Color based on Generator1.Low_oil_pressure (Critical-Red)

  • Engine Speed - (Generator_1.Engine Speed)

    • Color based on Generator_1.Over_Speed, Generator_1.Under_Speed (Urgent-Orange)

  • Frequency (Generator_1.Gen_Frequency)

    • Color based on Generator1.Frequency_High, Generator1.Frequency_Low (Urgent-Orange)

  • Phase 1 - Voltage, Current (Generator_1.Gen_V1, Gen_I1)

    • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. 

    • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

  • Phase 2 - Voltage, Current (Generator_1.Gen_V2, Gen_I2)

    • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. . 

    • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

  • Phase 3 - Voltage, Current (Generator_1.Gen_V3, Gen_I3)

    • Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Output High Voltage Threshold. . 

    • Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Output Minimal Voltage Threshold

  • Grid Voltage - phases 1-3 (Generator_1.Grid_V1, V2, V3). display only of site layout containing "ONGRID"

  • Alarms - display the active digitals under the group Generator_1 with color according to the severity. Include also fuel digitals from site global:

    • Fuel_1 Low

    • Fuel_1 VeryLow

    • Alarm_FuelTank_Hatch_1

    • Fuel_1 Disconnected

    • Not includes the following digitals under Generator_1 - Alarm_Active, Alarm_Critical, Alarm_Urgent, Alarm_Non_Urgent, Alarm_Indication

Generator Relay

Configurations->DG1_Running is true and Generator_1.Configured is false.