Field Name | Field Description |
---|---|
Generator X Initial Engine Hours |
|
Generator X Final Engine Hours | |
Generator X Total Engine Hours | The total hours the engine was running in the selected time range. Based on the field Site_Global.DGX_Engine_Hours. |
Generator X Overall [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (including drops) and the engine hours. |
Generator X Overall Fuel [Liter] | The total amount of fuel consumed (including fuel drops) in the selected time range. |
Generator X Operational Consumption [Liter/H] | The fuel rate of the generator in terms of a liter per hour. The fuel rate is calculated according to the fuel consumed (not including drops) and the engine hours. |
Generator X Operational Fuel [Liter] | The total amount of fuel consumed (not including fuel drops) in the selected time range. |
Generator X Fuel Drops | Number of fuel drops in the selected time range. In order to collect this data, a fuel drop event must be created - Fuel Events* |
Generator X Total Fuel Drop [Liter] | The total amount of fuel that was lost as a result of fuel drops. In order to collect this data, a fuel drop event must be created - Fuel Events* |
Generator X Refuels | Number of refuels in the selected time range. |
Generator X Total Refueled [Liter] | The total amount of fuel that was refueled in the selected time range. |
Generator X Ignition Count | Number of generator ignitions during the selected time range. |
Generator X Initial Fuel [Liter] | The fuel level of the generator in the first/last record in the selected time range. |
Generator X Final Fuel [Liter] | |
Generator X Minimum Fuel Level [Liter] | The minimum fuel level value of the generator in the selected time range. |
Generator X Frequency Max [Hz] | The minimum and a maximum frequency of the generator in the selected time range. |
Generator X Frequency Min [Hz] | |
Generator X Battery Voltage Max [V] | The minimum and a maximum voltage of the generator's battery in the selected time range. |
Generator X Battery Voltage Min [V] | |
Generator X Oil Pressure Max, Min, Avg* [kPa] | The minimum, maximum and average oil pressure of the generator in the selected time range. |
Generator X Total Flow Meter Fuel [Volume] | Fuel consumption from a dedicated sensor (Flow Meter) on a daily basis. |
Generator X Average Flow Rate [Volume\Hour] | The daily average of fuel that passed through the sensor (Flow Meter per hour. |
| When the 'standard' data for the fuel consumption rate (Generator X Operational consumption [Liter/Hour]) exceeds the logical range, the new field calculates the estimated fuel consumption by estimating the fuel consumption based on the generator's load and KVA. When “Y” and “X” are coefficients that change according to the generator's KVA. |
| Whenever there's an illogical result in the system fuel consumption parameters (Generator X Operational Consumption [Liter/H]), the CPH field will show an estimated consumption based on the generator's load and the KVA. Logic:
|
*Zeros are ignored in the calculation of averaged fields