The Generator card will appear on the screen only if Generator_1.Configured is true Or Fuel_1. Configured is true, or Configurations → DG1 Generator 1 Running is true.
...
Main View
"On/Off" sign - green and "On" if the generator is running, yellow and "Off" otherwise. If the device is disconnected, the text will be according to Site_Global.DGGenerator_Running unning (On/Off), but the color will be gray. In the status bar, a time counter will appear if the generator is running.
Alarms indication and number (for the list of alarms see Expand) - the color of the alarm bar will be the color of the most critical alarm.
Fuel Level (Site Global Fuel 1) - Colors for the fuel data:
Orange (urgent alarm) If Site_Global_Fuel_1_Low is true
Red (critical alarm) If Site_Global_Fuel_1_VeryLow is true
If Fuel_1_Disconnected is true, the disconnected icon will appear next to the Fuel Level title, and the color of the value will be gray.
Load - DG1Generator1_Load_Power
Working Mode (Generator_1.Working_Mode)
Color based on Generator1.Not_in_AutoMode - (Urgent-Orange)
...
The fuel level, load, and world mode are the same as in the main view.
Control button - clicking
The following configuration is required to be able to use the remote control option of the generator that is connected to a panel: Manager >> My units >> Choose the unit >> Configuration tab >> Device Configuration >> Section Generators >> Generator X Panel >> V
Clicking the control will open a drop-down with the options:
Engine Start, Engine Stop - Use the generator control panel to start and stop the generator
Auto Mode, Stop Mode, Manual Mode
Test On Load Mode
Alarms Reset, and Alarms Reset 2
Output - On, Output - Off - Use the Galooli gateway output to start and stop the generator.
After clicking one of the options, a confirmation message will appear as a popup. "Are you sure? The selected command will be applied to the generator".
...
Engine Hours - Generator_1.Engine_Hours
Coolant Temp (Generator_1.Coolant Temp)
Color based on Generator1.High_Coolant (Urgent-Orange), Low_Coolant (Non-Urgent-Yellow)
Battery Level (Generator_1.Battery_Level)
Color if Generator1.Battery_High Or Generator_1.Battery_Low (Urgent-Orange)
Oil Pressure - (Generator_1.Oil Pressure)
Color based on Generator1.Low_oil_pressure (Critical-Red)
Engine Speed - (Generator_1.Engine Speed)
Color based on Generator_1.Over_Speed, Generator_1.Under_Speed (Urgent-Orange)
Frequency (Generator_1.Gen_Frequency)
Color based on Generator1.Frequency_High, Generator1.Frequency_Low (Urgent-Orange)
Phase 1 - Voltage, Current (Generator_1.Gen_V1, Gen_I1)
Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Generator Output High Voltage Threshold.
Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Generator Output Minimal Voltage Threshold
Phase 2 - Voltage, Current (Generator_1.Gen_V2, Gen_I2)
Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Generator Output High Voltage Threshold. .
Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Generator Output Minimal Voltage Threshold
Phase 3 - Voltage, Current (Generator_1.Gen_V3, Gen_I3)
Color phase voltage if Generator_1.High_voltage (urgent) is true, and the phase voltage > DG Generator Output High Voltage Threshold. .
Color phase voltage if Generator_1.Low_voltage (urgent) is true, and the phase voltage < DG Generator Output Minimal Voltage Threshold
Grid Voltage - phases 1-3 (Generator_1.Grid_V1, V2, V3). display only of site layout containing "ONGRID"
Alarms - display the active digitals under the group Generator_1 with color according to the severity. Include also fuel digitals from site global:
Fuel_1 Low
Fuel_1 VeryLow
Alarm_FuelTank_Hatch_1
Fuel_1 Disconnected
Not includes the following digitals under Generator_1 - Alarm_Active, Alarm_Critical, Alarm_Urgent, Alarm_Non_Urgent, Alarm_Indication
...
Generator Relay
Configurations->DG1>Generator1_Running is true and Generator_1.Configured is false.