Power Troubleshooting

How to Detect the Fault?

Fault Description

Troubleshooting Steps









There is no blinking of the power red LED

Image Added







When the meter is connected to the power source, it does not receive any power

  1. Make sure the positive wire is connected to pin 7 and the negative wire is connected to pin 8.

...

  1. Image Added
  2. Make sure the power supply is 12 volts DC.

...

  1. On the AC meter side

...

  1. , make sure the cable is not broken

...

A Communication Issue With RS485 (AC connected directly to a computer)

...

  1. .

    Image Added


Power Center Communication Troubleshooting

How to Detect the Fault?

Fault Description

Troubleshooting Steps






















The AC meter connection state is “No Connection”

Image Added




























Elara connected but the AC meter displayed “No connection”

  1. The AC meter's LEDs should be blinking and the power supply should be on.

    Image Added
  2. Check that RS485 A and RS485 B cables are connected correctly (RS485 A = pin 16, RS485 B = pin 15).

...

  1. Image Added

  2. Ensure the

...

  1. communication cables (RS-485) is in good condition and not broken or overly long (up to 15 meters).

  2. Make sure the baud rate

...

No Communication to Power Center (Elara connected but AC meter display as “not connected”)

...

The AC meter's LEDs should be blinking and the power supply should be on

...

  1. of the meter is 19200 and the device ID is according to your wiring diagram.

    Image Added
  2. Verify that Port 1 on the Elara is

...

  1. “host”.

...

  1. Image Added

...



Negative Current

...

  1. Change the phase direction according to the wiring diagram

    Image Removed

AC Meter Displays a Wrong Voltage

...

Verify the voltage L1 and Current L1 are both on L1 (same for L2 and L3)

Verify Neutral is connected to pin 4 on the faze side

...

& Power Factor Troubleshooting

How to Detect the Fault?

Fault Description

Troubleshooting Steps

The Current & Power factors are negative

Image Added










A negative reading is obtained because the power source cable passes through the current ring in the wrong direction

  1. As shown in the picture below, make sure the phase direction is correct

    Image Added


Wrong Voltage Troubleshooting

How to Detect the Fault?

Fault Description

Troubleshooting Steps






The voltage reading is higher than allowed

Image Added









The phases cables of the AC ring connected to the wrong pins in the AC meter

  1. Verify you connect the cables from the CT ring to the AC meter according to the relevant phases.

    Pin 1 > Phase 1 Current
    Pin 2 > Phase 2 Current
    Pin 3 > Phase 3 Current
    Pin 4 > Neutral

    Image Added