Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

The smoke detector detector’s purpose is to monitor any presence of smoke/fire and to give off an alarm when detected on-site by sending its readings through an IoT unit to the Galooli server.

...

Features

...

  • Monitors for the presence of smoke and/or fire and gives off an alarm when detected

  • External power required

  • Indoor use only

Technical Specification

...

Diameter

101 mm including base

Height (including base and LED)

52 mm

Weight

106 gr.

Operating Temperature Range

-10°C - +60°C (14°F - 140°F)

Relative Humidity Range

10% - 93% non-condensing

Sensitivity Range

1.8%±0.5% / foot obscuration

Operating Voltage (supplied by control panel via SLC)

12-28 Vdc

Standards and Certifications

  • CE Marking

  • UL 268

  • EN 54-7

  • RoHS Compliance

  • ISO 9001

  • EN 50130-4

  • EN 61000-6-2

  • FCC Part 15 (if applicable)

Additional Information

  • Manufacturer PN. - TFB-180RL + TFO-480

  • Galooli PN. - 400-SmokeT440-843

  • Manufacturer datasheet

View file
nameTFO-480En102480AEn101.pdf

...

Max current consumption (quiescence mode):

...

120μA

...

Max current consumption (alarm mode without auxiliary indicators):

...

27mA

...

Max current consumption (3 auxiliary indicators):

...

35mA

...

Max current to auxiliary indicators:

...

50mA

...

View file
nameTFB-180En102.pdf

Pinout Diagram

Color

Name

Black

GND terminal

Yellow

Elara/EX device

Output

White

+12V

...

Recommended configuration for Galooli gateways:

  • Manufacturer configuration software

  • Recommended Galooli gateways:

Elara

Corona

...