This document describes the ethernet connection between the Elara gateway and the Cerbo Victron GX. It then describes the process for configuring the Cerbo Victron GX system virtual device.

For this connection to be established, a A router with at least three ethernet ports is required for this connection to be established.

Connectivity to the Cerbo GX

...

Connection and Configuration Processes

  1. Ensure that your router has at least three Ethernet ethernet portsחיברתי את הראוטר למחשב שלי ולאחר מכן הצלחתי לגלוש ללא בעיה, לא עשיתי שום שינוי בהגדרות של הראוטר.
    בדיקה שהאינטרנט עובדנכנסים לכתובת האינטרנט של הסרבו ומבטלים את הווי פי והבלוטוס .

  2. Through the ethernet connection, connect the router to your computer.

  3. Write down the IP address of the router in the computer's network configuration. Open any browser and verify that you are able to access different websites.

  4. Connect the Victron Victron-GX to the router while the router is connected to the computer.

  5. It is necessary to cancel the Wifi settings of the Victron Victron-GX. To cancel Wi-Fi settings on the Victron Victron-GX, click the following link-https://vrm.victronenergy.com/installation-overview
    לאחר מכן חיברתי את הסרבו לראוטר. וידאתי שהסרבו מקבל אינטרנט מהראוטר על ידי ניתוק ה WIFI והבלוטוס מההגדרות של יחידת הסרבו.
    כמו כן, ברגע שאני עושה לוגין לאתר של VRM – אני מצליח לעשות Remote Console.

4. צעד הבא היה לחבר באמצעות כבל רשת יחידה אלרה לבין הראוטר.
בפאוור סנטר הוספתי ModBus ETH Device – VICTRON_CERBOGX_System

5.שיניתי את ה IP כך שיהיה תואם ל IP  שיש כרגע ב Cerbo, כמו כן שיניתי את ה IP  באלרה שיהיה בטווח הנכון.
ראיתי חיבור תקין בפאוור סנטר.

צריך לוודא שהIP של הסרבו בטווח של האלרה על ידי שינוי האלרה בהתאם לסרבו

לוודא חיבור סופי

לשמור שינוים

*הערה בנוגע לכל ה virtual id של Cerbo –

כולם ID 100 בברירת מחדל, במידה וטכנאי לא ישים לזה לב וינסה להוסיף מספר מכשירים, הוא יראה רק מכשיר אחד, אולי אפשר לשנות את ה ID הווירטואלי ככה שלכל אחד יהיה מספר שונה?

Configuration Via Ethernet Method

  1. Network (Static settings): Settings → Ethernet →

...

b. Modbus TCP: Settings → Services →

...

c. To find the connected devices IDs, Settings → Services → Modbus TCP (ENABLED) → Available Services

[note: There is no device connected in this example, so only the gateway 'system' is visible]

...

...

  1. :

    1. Enter the username and password provided by the supplier

      Image Added

    2. Make sure that the Victron Victron-GX receives a network signal from the router. "Last update" should reflect the most recent time and date.

      Image Added

    3. Click on “Remote Console” >> Settings >> Wi-Fi >> Create access point should be set to “Off”.

    4. Click on “Remote Console” >> Settings >> Services >>Modbus TCP >> “Enable”

      Image Added

      e. On the same screen, click on the arrow from the right of the “Enable” word and enter the relevant IDs.

      Image Added

  2. Connect the Elara gateway to the router using an Ethernet cable

Configuration

  1. Connect the computer to the Elara via serial connection - https://galooli.atlassian.net/l/cp/ffa16RY7

  2. Make sure the Elara Ethernet port version is up-to-date - https://galooli.atlassian.net/l/cp/5fRL1DfX

  3. Copy the Victron Victron-GX IP address via https://vrm.victronenergy.com/installation-overview:
    Click on “Remote Console” >> Settings >> Ethernet >> IP address.

    Image Added

  4. Add the Victron Victron-GX to the Elara gateway. Verify that the IP address is the same as that mentioned in the previous step

...


5. Click on “Write Configuration

Victron GX Components Configuration Process

Following successful connection to the Cerbo Victron GX and configuration via the Power Center, the CerboVictron-GX can display its components in two different ways:

  • The configuration of the “Cerbo“Victron-GX system" component provides a unified view of all the various components that can be connected to CerboVictron-GX. It provides a relatively complete picture but with fewer data points

  • Configuring each component separately